TopTherm Blue e roof-mounted cooling unit Total cooling output 0.50 - 4.00 kW

Article number: SK 3386.540

Energy-efficient Blue e roof-mounted cooling units in output categories from 500 W to 4,000 W with e-Comfort controller integrated as standard and electrical condensate evaporation.

Article number:
SK 3386.540
Product description
Energy-efficient Blue e roof-mounted cooling units with integral e-Comfort controller and electric condensate evaporation as standard.
Benefits
May be linked to the IoT interface via Blue e IoT adaptor for cooling units from 500 W cooling output with e-Comfort controller
Material
Sheet steel
Colour
RAL 7035
Supply includes
Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts
Total cooling output to DIN EN 14511
Cooling output L35 L35/50 Hz: 3 kW
Cooling output L35 L35/60 Hz: 3.3 kW
Cooling output L35 L50/50 Hz: 2.2 kW
Cooling output L35 L50/60 Hz: 2.5 kW
Rated operating voltage
400 V, 3~, 50 Hz
460 V, 3~, 60 Hz
Note
The roof-mounted cooling unit 3273.500 is also suitable for office applications, thanks to its low noise level.
Rated current max.
At 50 Hz: 3.4 A
At 60 Hz: 3.4 A
Start-up current max.
At 50 Hz: 8 A
At 60 Hz: 9 A
Air throughput (unimpeded air flow)
External circuit: 3,450 m³/h
Internal circuit: 1,280 m³/h
Energy efficiency ratio (EER) 50/60 Hz L35 L35
Refrigeration factor L35 L35 (EER) 50 Hz: 2.56
Refrigeration factor L35 L35 (EER) 60 Hz: 2.23
Design
roof-mounted
Dimensions
Width: 796 mm
Height: 470 mm
Depth: 580 mm
Protection category to IEC 60 529
External circuit IP 34
Internal circuit IP 54
Refrigerant/cooling medium
Refrigerant: R134a
Quantity: 1.6 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 2.29 t
Type of electrical connection
Plug-in terminal strip
Duty cycle
100 %
Temperature control
e-Comfort controller (factory setting +35 °C)
Operating temperature range
10 °C...55 °C
Storage temperature range
-40 °C...70 °C
Setting range
20 °C...55 °C
Power consumption Pel
Power consumption L35 L35/50 Hz: 1.17 kW
Power consumption L35 L35/60 Hz: 1.48 kW
Power consumption L35 L50/50 Hz: 1.42 kW
Power consumption L35 L50/60 Hz: 1.76 kW
Permissible operating pressure (p. max.)
28 bar
Pre-fuse
Motor circuit-breaker: 6.3...10 A
Packs of
1 pc(s).
Weight/pack
70 kg
Customs tariff number
84158200
EAN
4028177323308
ETIM 7.0
EC000855
ECLASS 8.0
27180704
Product description
SK cooling unit Blue e, roof-mounted, 3 kW, 400-460 V, 3~, 50/60 Hz, Sheet steel, WHD: 796 x 470 x 580 mm
Approvals
CSA
UL + C-UL - FTTA
UR + C-UR (recognized)
Certificates
EAC
Declarations
Declaration of conformity
Declaration of conformity - F-gas regulation
Declaration of conformity UK
Documentation
Instructions
Safety instructions
White Paper
Data sheets
Safety data sheet refrigerant
Technical details
Technical system catalogue
3386540
Roof-mounted cooling unit TopTherm Blue e
Energy-efficient Blue e roof-mounted cooling units with integral
e-Comfort controller, hydrophobic RiNano coating on the condenser and e
condensate evaporation as standard.
Total cooling output L35 L35 50/60 Hz: 3,0 / 3,3 kW
Total cooling output L35 L50 50/60 Hz: 2,2 / 2,5 kW
Power consumption L35 L35 50/60 Hz: 1,17 / 1,48 kW
Power consumption L35 L50 50/60 Hz: 1,42 / 1,76 kW
Rated power input 50/60 Hz: 3,4 / 3,4 A
Rated operating voltage: 400 V - 460 V, 3~, 50/60 Hz
Temperature control: e-comfortcontroller (factory setting +35 °C)
Dimensions [WxHxD]: 796x470x580 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,56 / 2,23
Refrigerant / Quantity: R134a / 1600 g
Operating temperature range: 10 °C to 55 °C
Setting range: 20 °C to 55 °C
Protection category IP to IEC 60 529: Internal circuit IP 54, external
circuit IP 34
Weight: 70 kg