Outdoor cooling unit for CS Toptec

Model No. 9776.550

  Product Lifecycle  
Expired
  • Outdoor cooling unit for CS Toptec

    Discontinued article.

    Information on the discontinued articles
    This item will be discontinued on 31.01.2021
    This item is being replaced by 3185330
    Wall-mounted cooling unit Blue e+ outdoor 1.5 kW – 5.0 kW
     

    Close
    Product details

    Useful cooling output/heater 1,400 W/400 W, temperature control via e-Comfort controller. For mounting on the CS Toptec in 3 positions: External, partial internal and full internal mounting.

    + Product description

    Product description: Temperature control via e-Comfort controller. The cooling unit may be attached to the enclosure in 3 positions (external, partial internal and full internal mounting).
    Benefits: May be linked to the IoT interface via Blue e IoT adaptor for cooling units from 500 W cooling output with e-Comfort controller
    Material: Aluminium
    Surface finish: Powder-coated
    Pure polyester
    Colour: RAL 7035
    Supply includes: Fully wired ready for connection (plug-in terminal strip)
    Mounting frame for universal attachment to outdoor enclosures for external, partial internal and full internal mounting.
    IP protection category to IEC 60 529: External circuit IP 34
    Internal circuit IP 55
    Total cooling output to DIN EN 14511: Cooling output L35 L35/50 Hz: 1.4 kW
    Cooling output L35 L35/60 Hz: 1.53 kW
    Cooling output L35 L50/50 Hz: 1.06 kW
    Cooling output L35 L50/60 Hz: 1.1 kW
    Heater output: 400 W
    Rated operating voltage: 230 V, 1~, 50 Hz/60 Hz
    Start-up current max.: At 50 Hz: 34 A
    At 60 Hz: 32 A
    Air throughput (unimpeded air flow): External circuit with 50 Hz: 1,000 m³/h
    External circuit with 60 Hz: 1,090 m³/h
    Internal circuit at 50 Hz: 880 m³/h
    Internal circuit at 60 Hz: 950 m³/h
    Rated current max.: At 50 Hz: 6 A
    At 60 Hz: 6.8 A
    Temperature control: e-Comfort controller (factory setting +35 °C)
    Operating temperature range: -33 °C...55 °C
    Setting range: 20 °C...55 °C
    Refrigerant/cooling medium: Refrigerant: R134a
    Quantity: 0.9 kg
    Global Warming Potential (GWP): 1,430
    CO₂ equivalent (CO₂e): 1.3 t
    Power consumption Pel: Power consumption L35 L35/50 Hz: 0.96 kW
    Power consumption L35 L35/60 Hz: 1.17 kW
    Power consumption L35 L50/50 Hz: 1.13 kW
    Power consumption L35 L50/60 Hz: 1.25 kW
    Permissible operating pressure (p. max.): 28 bar
    Dimensions: Width: 500 mm
    Height: 1,000 mm
    Depth: 274 mm
    Enclosure dimensions including sealing frame and designer cover: Width: 552 mm
    Height: 1,052 mm
    Depth: 274 mm
    Energy efficiency ratio (EER) 50/60 Hz L35 L35: Refrigeration factor L35 L35 (EER) 50 Hz: 1.46
    Refrigeration factor L35 L35 (EER) 60 Hz: 1.31
    Pre-fuse: Miniature circuit-breaker/fuse: 10 A
    To fit: Enclosure type: CS Toptec
    Width: ≥ 800 mm
    Height: ≥ 1,200 mm
    Installation type: Universal installation (external mounting, partial internal mounting, full internal mounting)
    Packs of: 1 pc(s).
    Weight/pack: 45 kg
    Customs tariff number: 84158200
    EAN: 4028177463110
    ETIM 7.0: EC000855
    ECLASS 8.0: 27180704

    + Approvals

    Declerations:
    Declaration of conformity: 
    DE, EN
    Declaration of conformity - F-gas regulation: 
    DE, EN

    + Downloads / CAD

    Data Sheets:
    Safety data sheet refrigerant: 
    CS DE EN ES IT JA PL SK
    Documentation:
    Instructions: 
    DE, EN

    + Add accessories

    + Tender texts

    Cooling unit 1600 W for outdoor use in the temperature
    range from -33° to +55°C
    For universal installation, partial internal mounting
    or external mounting on side panels, rear panels or
    doors of outdoor enclosures, minimum enclosure
    dimensions WxH 800 x 1200 mm.
    With microcontroller for temperature control and
    monitoring, diagnostics and evaluation of error
    messages of the cooling unit. The protection category
    of IP 55 for the enclosure is retained due to the
    separation of internal circuit and external circuit.

    Installation: Universal installation, the unit can
    optionally be mounted on the special mounting frame
    with all-round seal on the inside, on the outside or
    partially internal. A later modification of the
    installation type is easily possible.
    Enclosure dimensions (mm) WxHxD 500 x 1000 x 235 mm
    Minimum enclosure dimension mm WxH or DxH: 800 x 1200

    Useful cooling output to EN 814:
    L35 L35 1600/1750 W
    L 35 L 50 1200/1250 W
    Coolant: R 134a
    Rated operating voltage: 230 V AC /50/60 Hz
    With integral heater, 400 W

    Type of connection: Female multi-point connector
    9-pole. Temperature control via microcontroller.

    Temperature range of environment -33°C to +55°C

    Material (enclosure): Aluminium
    Surface finish: Spray finished in RAL 7035

    Protection category (internal circuit to external
    circuit):
    IP 55 to EN 60529/10.91

    Model:
    Rittal

    Type:
    Toptec cooling unit CS 9776.550 or equivalent

     Outdoor cooling unit for CS Toptec

    Model No.

    Close
    +
    [X] Close

    Required 

    $nbsp;

    Product data (ZIP)

    Rittal does not assume any liability for the topicality of the data downloaded locally on your device.

     I agree

    Close