RiMatrix S Standard container

Model No. 7998.206

  Product Lifecycle  
Expired
  • RiMatrix S Standard container
  • RiMatrix S Standard container

    Discontinued article.

    Information on the discontinued articles
    This item will be discontinued on 30.06.2023

     

    Close
    Product details

    The standardised data centre is implemented in a container solution and can therefore be sited outdoors if required.

    + Product description

    Product description: The standardised data centre is implemented in a container solution and can therefore be sited outdoors if required.
    Supply includes: Robust sheet steel container with reinforced frame structure for optimum weight distribution
    Housed interior wall structure with thermal insulating materials
    Advice and ROI calculation
    Delivery and integration into the customer infrastructure
    Documentation, training and instruction
    Hotline and service/service agreements
    Clearance depth: 7,000 mm
    Clearance height: 2,700 mm
    Clearance width: 2,750 mm
    Climate control (ZUCS): 60 kW + 10 kW
    n+1 redundant
    Number of low-voltage main distributors: 1
    No. of PDU Basic: 14
    Serverracks (600x2000x1200mm): 6
    Combined network/server rack (800 x 2000 x 1200 mm): 1
    Protection standards: Vandal-proof interior in accordance with Resistance Class II to DIN EN 1631
    EMC basic protection
    Dust- and watertight to IP 55 to IEC 60 529
    Design burglar protection: yes
    Humidification and dehumidification system: optional
    Room extinguisher system: optional
    Design UPS: 60 kW + 20 kW
    n+1 redundant
    Version: Single 6
    Dimensions: Width: 3,000 mm
    Height: 3,000 mm
    Depth: 7,250 mm
    Packs of: 1 pc(s).
    Customs tariff number: 85371098
    EAN: 4028177702486
    ETIM 7.0: EC002499
    ECLASS 8.0: 27180207
    Product description: DK RiMatrix S Standard container, Single 6

    + Downloads / CAD

    + Tender texts

    Standard data centre 60 kW, 6+1 racks,
    including cooling and UPS, installed in a container,,
    ,,,,,,
    Fully functional data centre comprising an ITC
    climate zone for the server and network systems, and a
    separate technical climate zone for the UPS equipment
    and low-voltage switchgear.

    The ITC climate zone comprises a rack suite (depth
    1200 mm) with 6 server racks and a network rack, and
    is fully isolated from the climate zone for the
    electrical equipment by way of self-closing sliding
    doors in the cold and hot aisles.

    The data centre is enclosed by an accurately
    dimensioned IT container.
    It is designed in the form of a steel
    container with water-tight, welded steel frame and
    zinc-plated sheet steel panelling.
    The IT container permits outdoor installation
    and eliminates potential physical threats. A
    partition which passes over the rack systems achieves
    targeted separation of the climate zones.
    The following qualities are achieved in
    accordance with the specified requirements:

    Fire protection EI30 to EN 1363 (wall, ceiling)
    Burglar resistance RC2 to EN 1627
    Dust ingress IP5X to EN 60529
    Water ingress IPX4 to EN 60529

    Electromagnetic compatibility (EMC) as per test
    certificate in respect of high-frequency interference
    and susceptibility

    The container is sealed all round. The underside is
    provided with a protective coating of two-component
    liquid plastic. Alongside an adhesive primer and an
    intermediate coat of two-component PUR single-layer
    paint, the container is painted in accordance with the
    corrosion category C4 long to EN 12944 (coating
    system no. A4.09). Two pockets for the forks of
    a lift truck, each 360 mm wide and 120 mm high,
    are provided at the standard spacing
    of 2050 mm. The container frame is provided with 8
    corner pieces to ISO 1161.
    The minimum dynamic load-bearing capacity of the
    container is 6 tonnes. The static load-bearing
    capacity is 12 tonnes. The minimum roof load capacity
    is 100 kg/m².
    The insulation of the container comprises a mineral
    wool core with zinc-plated sheet steel sandwich panels
    on both sides, attached to sheet metal profiles at the
    roof and base. The inside floor in the form of plain
    sheet steel is bolted permanently to the underfloor
    construction. All-round edging of the same serves to
    produce a water-tight weld. An earthing point is
    provided.
    The outer skin of the cell is realised such as to
    avert external influences from the building and thus
    eliminate damage to the insulation materials.
    An access door is supplied and assembled as a
    single-door system hinged on the right-hand side (DIN
    definition).
    The door system is certified in accordance with the
    aforementioned test criteria. Corresponding proof is
    to be furnished by the supplier.
    The double-panelled security door is provided with an
    all-round seal. It features an electric security lock,
    top door closer, locking monitoring (bar contact),
    opening sensor (reed switch) and panic release.
    Nominal door dimensions:
    Width,,1125 mm
    Height,,2125 mm


    The 600 mm wide hot aisle and the 950 mm wide cold
    aisle are partitioned within the container
    and are to this end provided with a partitioning panel
    which passes over the server/network racks.

    The standard data centre incorporates a fully
    functional raised-floor construction, with air intake
    and outlet grilles in the form of dip-galvanised
    gratings.

    Air-circulating cooling units (CRAC systems) are
    installed in the cavity space of the raised floor. The
    CRAC systems do not occupy space within the rack (Zero
    U-Space Cooling Systems).

    A CRAC system is installed under each server rack.
    Each CRAC system offers a nominal cooling output of 12
    kW; the average heat load capacity per rack is thus 10
    kW, taking into account n+1 redundancy over the total
    number of CRAC systems.

    The intake temperature for cooling is 20°C, observing
    temperature limit values according to ASHRAE 2008
    (max. 27°C) within the cold aisle.

    The UPS climate zone possesses a further CRAC system
    to dissipate the UPS heat loss. Through direct
    injection of the UPS cooling air, a temperature level
    of max. 22°C is maintained within the climate zone, in
    accordance with the Eurobat guidelines on the
    environment for 10-year batteries.

    The cooled intake air is blown into the cold aisle by
    EC fans under the floor gratings. Flat filter fleeces
    are fitted between the fan grilles and the floor
    gratings to filter the circulating air.

    The intake temperature and speed of the EC fans are
    regulated by a controller in the standard data centre,
    which communicates with the controller of an optional
    chiller station via a system bus for purposes of
    energy efficiency optimisation. The controller is not
    accommodated in the IT racks and thus does not occupy
    rack installation space.

    The standard data centre is equipped ready for use
    with a cold piping system comprising polypropylene
    piping; the individual heat exchangers are connected
    by way of high-pressure hoses.


    Required chiller set provided by the customer:
    The standard data centre must be equipped with a
    straight ball valve to regulate the air intake
    temperature to the target value, a flowmeter and two
    temperature sensors to measure the coolant flow volume
    and the feed and return temperatures, as well as to
    calculate the heat output.

    Required chiller set must be supplied:
    The standard data centre must be supplied without ball
    valve and sensors for the coolant.
    The volume of the medium is regulated by the
    variable-speed pump of the chiller station of the
    standard data centre, and the sensors are fitted in
    the chiller station.

    The standard data centre is equipped with a modular
    UPS system with 20 kW modules. The system provides
    for n+1 redundancy, and thus four UPS modules
    are supplied to cover the possible connected load of
    60 kW for the ITC hardware.

    The UPS system possesses 10 battery strings with 28 Ah
    batteries, which are assigned jointly to all UPS
    modules and ensure autonomy for a period of 13
    minutes.

    The standard data centre incorporates switchgear with
    fused feeders for the installed rack suite. The
    switchgear spreads the feeders over two panels to
    establish an A/B power supply. The UPS system feeds
    supply path A. Supply path B must be connected to the
    mains supply via overvoltage protection.

    From the switchgear, the distribution busbars of the
    individual racks are wired ready for use and comprise
    Power Distribution Units with 24 C13 and 6 C19
    sockets. Each rack is provided with two PDUs to
    establish an A/B power supply.

    The power supply is routed above the racks. The data
    cables are routed to the IT racks separately from the
    power supply cables. The installation of the data
    cables is to be performed by the site
    operator/customer.

    Lighting and service socket are protected by way of an
    RCCB. Emergency lighting is installed.

    The standard data centre is equipped with an early
    fire detection system. To this end, air is drawn from
    the raised floor of the hot aisle via a perforated
    plastic pipe. The alarm is given by a monitoring
    system with Web access and SNMP interface.

    The scope of supply includes delivery and installation
    of the cable and piping bulkhead to bring the data,
    control and supply cables into the IT container
    (without IT cabling; connection to the chiller and
    mains power supply are to be ordered separately).



    Standard data centre version with 6+1 racks in
    container
    ,,

    Outside dimensions,,Inside dimensions,,
    Length:,,7250 mm,,Length:,,7000 mm,,
    Width:,,3000 mm,,Width:,,2750 mm,,
    Height:,,3000 mm,,Height:,,2685 mm,,
    ,,,,,,