Discontinued article.
Information on the discontinued articles
This item will be discontinued on 31.12.2021
Alternative product recommendation 3313460
Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC
Alternative product recommendation 3313460
Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC
Close
More on the product
Create PDF of this page+ Also required
+ Product description
Design: | LCP Inline DX/FC |
---|---|
Benefits: |
Maximum energy efficiency due to EC fan technology and IT-based control Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans Temperature monitoring and control With redundant temperature sensor integrated at the air end as standard Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements Specific maintenance of the LCP DX due to separation of cooling and server racks Using LCP DX/FC variants in combination with indirect free cooling helps to save operating costs |
Applications: |
Ideal for IT cooling of small and medium-sized locations One or two racks can be cooled separately |
Function principle: |
The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling. The LCP DX/FC variants include both a refrigerant and a water/glycol heat exchanger. There is an additional free cooler integrated into the external condenser. Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room |
Material: | Sheet steel, spray-finished |
Options: |
Humidifier Dehumidification and reheater Condensate drain pump Low-temperature/high-temperature condenser (-40 °C/+53 °C) |
Design: | Suite cooling |
Monitoring: |
Direct connection of the unit via SNMP over Ethernet Integration into RiZone |
Note: | Variant with UL approval available on request |
Total cooling output to DIN EN 14511: | Useful cooling output L22 L30: 35 kW |
Modulation range: | 8 ‐ 35 kW |
Total cooling output/Number of fan modules: | 35 kW/3 |
Air throughput (unimpeded air flow): | At 50 Hz: 9,900 m³/h |
Dimensions: |
Width: 600 mm Height: 2,000 mm Depth: 1,000 mm |
To fit enclosure type: | TS IT |
Installation in bayed enclosure suite: | Flush |
Rated operating voltage: |
380 V - 480 V, 3~, 60 Hz 400 V, 3~, 50 Hz |
Rated current max.: | At 50 Hz: 31.6 A |
Max. cooling output: | 35 kW |
Type of electrical connection: | Connection clamp |
Duty cycle: | 100 % |
Cooling medium: | Water/glycol |
EC fan: | yes |
SNMP card: | yes |
Fans may be exchanged with the system operational: | yes |
Temperature control: |
Linear fan control Inverter-controlled compressor |
Pre-fuse: | Miniature circuit-breaker/fuse: 40 A |
Operating temperature range: | 15 °C...35 °C |
Noise level: | At 50 Hz: 69 dB(A) |
Protection category to IEC 60 529: | IP 40 |
Packs of: | 1 pc(s). |
Weight/pack: | 398 kg |
Customs tariff number: | 84158200 |
EAN: | 4028177691360 |
ETIM 8: | EC002515 |
ETIM 7.0: | EC002515 |
ECLASS 8.0: | 27180712 |
Product description: | SK LCP Rack DX, WHD: 600x2000x1000 mm, 35 kW |
+ Approvals
Declerations: |
Declaration of conformity:
DE, EN
|
---|