Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

Model No. 3311.440

  Product Lifecycle  
Expired
    Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

    Discontinued article.

    Information on the discontinued articles
    This item will be discontinued on 31.12.2021
    Alternative product recommendation 3313440
    Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC
     

    Close
    Product details

    Ideal for cooling of small and medium-sized IT applications.

    + Also required

    + Product description

    Design: LCP Inline DX
    Benefits: Maximum energy efficiency due to EC fan technology and IT-based control
    Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
    Temperature monitoring and control
    With redundant temperature sensor integrated at the air end as standard
    Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements
    Specific maintenance of the LCP DX due to separation of cooling and server racks
    Using LCP DX/FC variants in combination with indirect free cooling helps to save operating costs
    Applications: Ideal for IT cooling of small and medium-sized locations
    One or two racks can be cooled separately
    Function principle: The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling.
    The LCP DX/FC variants include both a refrigerant and a water/glycol heat exchanger. There is an additional free cooler integrated into the external condenser.
    Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
    Material: Sheet steel, spray-finished
    Options: Humidifier
    Dehumidification and reheater
    Condensate drain pump
    Low-temperature/high-temperature condenser (-40 °C/+53 °C)
    Design: Suite cooling
    Monitoring: Direct connection of the unit via SNMP over Ethernet
    Integration into RiZone
    Note: Variant with UL approval available on request
    Total cooling output to DIN EN 14511: Useful cooling output L22 L30: 12 kW
    Useful cooling output L22 L45: 10 kW
    Modulation range: 3 ‐ 12 kW
    Total cooling output/Number of fan modules: 12 kW/4
    Air throughput (unimpeded air flow): At 50 Hz: 4,800 m³/h
    Dimensions: Width: 300 mm
    Height: 2,000 mm
    Depth: 1,200 mm
    To fit enclosure type: TS IT
    Installation in bayed enclosure suite: Flush
    Rated operating voltage: 380 V - 480 V, 3~, 60 Hz
    400 V, 3~, 50 Hz
    Rated current max.: At 50 Hz: 7.5 A
    Max. cooling output: 12 kW
    Type of electrical connection: Connection clamp
    Duty cycle: 100 %
    Cooling medium: Refrigerant
    EC fan: yes
    Fans may be exchanged with the system operational: yes
    Temperature control: Linear fan control
    Inverter-controlled compressor
    Pre-fuse: Miniature circuit-breaker/fuse: 20 A
    Storage temperature range: -20 °C...50 °C
    Operating temperature range: 15 °C...35 °C
    Noise level: At 50 Hz: 69 dB(A)
    Protection category to IEC 60 529: IP 20
    Packs of: 1 pc(s).
    Weight/pack: 233.5 kg
    Customs tariff number: 84195080
    EAN: 4028177691346
    ETIM 8: EC002515
    ETIM 7.0: EC002515
    ECLASS 8.0: 27180712
    Product description: SK LCP Inline DX, Refrigerant-based split cooling unit for suite cooling, Mounted on the side of the rack, flush, Cooling of several racks, Support of IT-compatible, #front-to-back# air routing,

    + Approvals

    Certificates:
    EAC: 
    RU
    Declerations:
    Declaration of conformity: 
    DE, EN

    + Downloads / CAD

    Data Sheets:
    Graphics: 
    DE EN
    Safety data sheet: 
    DE
    Technical Data sheet: 
    DE EN

    + Add accessories

    + Tender texts

    Tender text for LCP Inline DX, 3311.440 WHD (mm)
    300x2000x1200

    LCP Inline DX:

    IT-optimised design, providing ideal support for
    "front-to-back" air routing for the 482.6 mm (19")
    installations.

    As a direct condenser, the integrated air/refrigerant
    heat exchanger guarantees a cooling output of up to 12
    kW with standard server enclosure dimensions, the
    lowest possible weight, and comprehensive
    possibilities for monitoring.
    The LCP Inline DX is mounted on the side of the rack.
    The warm server air is drawn in through a perforated
    rear door and the cooled air is blown back via a
    perforated door in front of the perforated doors of
    the server rack and is thus made available to the
    482.6 mm (19") equipment once more.
    The LCP Inline DX is closed up to the server rack at
    the front and rear and there forms a flush joint with
    the rack.

    In its maximum configuration, the unit is equipped
    with four EC fans, for maximum efficiency and minimum
    power consumption.
    The flow characteristics of the heat exchanger are
    optimised for the lowest possible pressure losses on
    the air side. This minimises the energy consumption of
    the fans.

    An integrated inverter with corresponding controller
    serves to regulate the speed of the installed
    condenser.
    This permits stepless adaptation of the output, also
    in partial-load operation, and by reducing energy
    consumption also achieves a reduction in operating
    costs.

    Alongside the compressor, the cooling circuit of the
    LCP Inline DX comprises a collecting tank, liquid
    separator, electronic expansion valve, optimised heat
    exchanger, high and low-pressure sensors, Schrader
    valves, filter dryer, non-return valve, high-pressure
    switch and shut-off devices.
    The refrigerant connections and the electrical power
    connection to the unit can be realised from above or
    below.
    The system comprising LCP Inline DX and external
    condenser must be filled with refrigerant R410a after
    installation at the site.

    The LCP Inline DX and the server rack remain separate
    from each other. This simplifies assembly and service
    work and excludes the need for unwanted access to the
    server rack for maintenance purposes.
    Maintenance and service for all relevant components
    can be realised quickly and simply thanks to the
    optimised layout. The fans can be exchanged quickly
    and at any time, even while the system is operational
    (hot swapping).
    The fans are installed in the cold air section, which
    increases their service life.
    .
    Condensate management is integrated into the unit. Any
    condensate is collected in a collecting tray in the
    base and from there discharged to the outside via a
    hose.

    Thanks to the integrated controller, the LCP Inline DX
    operates fully autonomously.
    The setpoint is the server intake air temperature,
    which is automatically held constant at the set value.
    Three sensors are present in each case for detection
    of the cold and warm air temperatures, providing for
    the appropriate redundancy.

    Monitoring and alarm management for all physical
    parameters is realised via SNMP and Ethernet.
    To this end, the optional SNMP card is required.

    A display with operating keys is integrated on the
    front of the unit to display and set the physical
    parameters.

    The external condenser SK 3311.360 is needed to
    operate the LCP Inline DX.
    Installation and commissioning on site, laying of the
    refrigerant pipes, and evacuation and filling of the
    system with refrigerant are not included in the scope
    of supply and must be realised by correspondingly
    qualified persons.

    Technical specifications:
    Useful cooling output:,,12 kW at 30 °C ambient
    temperature at place of installation of the ,,,,,,
    condenser
    10 kW at 45° C ambient temperature at place of
    installation of the condenser
    The LCP DX is modulating it´s cooling performance in a range between
    3-12kW without interference.

    Installed fans: 4
    Air throughput: max.5.000 m³/h
    Intake temperature, set: 22 °C
    Connection, liquide side: 12 mm, external thread
    Connection, gas intake side: 12 mm, external thread
    Power supply:,,400 V, 3~, N, PE, 50/ 60 Hz (voltage
    range 380-460 V)
    Max. connected load: 4,700W
    Refrigerant: R410a
    Connection length, max.: 30 m
    Height difference (condenser higher/lower), max:
    20/3 m
    Dimensions (WxHxD): 300x2000x1200mm
    Weight: 180 kg
    Colour: RAL 7035

    Available installation space in adjoining server rack:
    Unrestricted (standard: 42 U)

    Accessories:
    SNMP card for network connection: 3311.320
    External condenser (needed to operate the LCP-DX):
    3311.360 3311.360

    Optional:
    If necessary, a humidifier and/or heater can be
    integrated into the LCP Inline DX.
    Please enquire for further details.