Liquid Cooling Package LCP Inline CW

Article number: SK 3311.568

Model no.: LCP 60KW, INLINE PROTRUDING, 4 FANS

These highly efficient Inline units can create a cold curtain down a row rather than simply moving air into an aisle.Available in two versions: Flush, a configuration where the unit’s face matches that of the adjacent enclosures and air flows into the racks, and Protruding where the unit is bumped out 8 inches into the aisle and cool air flows from both sides across the face of nearby enclosures.The unit’s high-efficiency fans have been moved to the front of the LCP – on the cool side away from maximum heat – which will extend the life of the fans. Water connections are available at either the top or bottom of the unit.

Article number:
SK 3311.568
Model no.:
LCP 60KW, INLINE PROTRUDING, 4 FANS
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal area load due to low weight
The separation of cooling and enclosure prevents water from entering the server enclosure
Redundant temperature sensor integrated at the air end
Fan modules configurable as n+1 redundancy.
Targeted cooling output thanks to modular box-type plug-in fan units
By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
Optimum adaptability due to dynamic, continuous control of the cold water volume flow
Minimal pressure loss at the air end, which in turn minimizes the power consumption of the fans
Up to 204728.52 BTU/h cooling output on a small footprint
Top or bottom feed water connection
Function principle
The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary
Color
Exterior: RAL 9005
Enclosure frame and interior: RAL 7035
Supply includes
Incl. 4 fan modules.
Options
Various sensors
Racks
Max. cooling output
60 kW
( 204,728 BTU/h )
Type of connection (electrical)
Connector
Air throughput per fan
4708 cfm (6 fans)
Cooling medium
Water
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Infinitely variable fan control
2-way control ball valve
Water connections
DN 40 (G 1½" external thread)
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage.
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Installation in bayed enclosure suite
Protruded
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
( Width: 11.8 ˝
Height: 78.7 ˝
Depth: 47.2 ˝ )
Total cooling output/number of fan modules
40 kW/4
50 kW/5
60 kW/6
( 136,486 BTU/h
170,607 BTU/h
204,728 BTU/h )
Water inlet temperature
15 °C
( 59 °F )
Packaging unit
1 pc(s).
Weight/packaging unit
210 kg
( 463 lb. )
Customs tariff number
8415830030
UPC-Code
87742
Approvals
UL
Documentation
Instructions
Data sheets
Data sheets
Technical Data sheet
Technical details