RiLineX 熔丝断路器 D 开关

型号: RX 9360824

RiLineX fuse-switch disconnector for 60 mm busbar systems. For use with D 01 (via gauge ring) and D 02 slow fuses (max. 63 A). Also for use with 10 x 38 mm cylindrical fuses via the supplied retaining springs. Integral optical LED fuse monitoring plus electronic fuse monitoring with alarm contacts The switch is lockable in the on and off positions. Spring terminal blocks up to 16 mm² at an angle of 45° enable easier conductor connection. The device is suitable for tool-free snap-on mounting with semi-automatic busbar adjustment for 5 and 10 mm.

型号:
RX 9360824
型式
带电子式熔丝监控
您的获益
熔断器插片的安全接触(无需螺丝帽)
支持卡扣式安装,可轻松适配 5/10 mm 厚度的母线
光学 LED 熔断器状态监测
通过独立开口进行电压测试
适用于最大 16 mm² 线径的免维护张力弹簧接线端子
无需螺丝帽等额外附件即可实现全面防触摸保护
材料
聚酰胺 (PA 6)
防火性能根据 UL 94
General colour
RAL 35745
RAL 9005
供货范围
4 个熔丝断路器
12 个用于 D 01 型熔断器的变径接头
额定电流 最大
63 A
导线出线
下面
极数
3 极
适合于母线系统
RiLineX
RiLine60
尺寸
宽度: 35.8 mm
高度: 263 mm
深度: 104.2 mm
圆导线连接,细线带电缆芯线套管
1.5 ‐ 16 mm²
连接圆导线,细绞线,带 AWG 冷压端头
AWG 16 ‐ AWG 6
圆导线连接,多芯
1.5 ‐ 16 mm²
连接圆导线,多股(AWG 标准)
AWG 16 ‐ AWG 6
适合于母线
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
过压类别
4
污染等级
3
标准
IEC/DIN EN 60 947-3
Rated insulation voltage
800 V
Power dissipation (max.)
5.5 W
防护等级 IP,符合 IEC 60 529 标准
IP 2XB
Operation humidity max
90 %
工作温度范围
-5 °C...55 °C
贮存温度范围
-25 °C...75 °C
空气湿度(没有凝露)
10...90 %
使用类别
AC-22B (400 V/100 A)
保险器熔丝
D 02-E 18
包装单元
4 件
净重
2.232 kg
毛重
2.236 kg
铜成分(kg/件)
0.105
税率号
85365080
ETIM 9
EC001040
产品描述
RiLineX fuse-switch disconnector for 60 mm busbar systems. For use with D 01 (via gauge ring) and D 02 slow fuses (max. 63 A). Also for use with 10 x 38 mm cylindrical fuses via the supplied retaining springs. Integral optical LED fuse monitoring plus electronic fuse monitoring with alarm contacts The switch is lockable in the on and off positions. Spring terminal blocks up to 16 mm² at an angle of 45° enable easier conductor connection. The device is suitable for tool-free snap-on mounting with semi-automatic busbar adjustment for 5 and 10 mm.
声明
符合性声明
资料
安全说明书
说明书
Quick guide
数据页
基本技术信息