Liquid Cooling Package LCP rack DX, LCP rack DX/FC

Article number: SK 3311.410

Rack-based cooling on one to two IT racks. Continuous cooling output adjustment due to the use of an output-controlled compressor in the LCP Rack DX (evaporator) An external condenser is required to operate the unit.

Article number:
SK 3311.410
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Control of the server inlet temperature
Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements
With redundant temperature sensor integrated at the air end as standard
Specific maintenance of the LCP DX due to separation of cooling and server racks
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
Material
Sheet steel, spray-finished
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Design
Rack cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Total cooling output to DIN EN 14511
Useful cooling output L22 L30: 12 kW
Useful cooling output L22 L45: 10 kW
Modulation range
3 ‐ 12 kW
Total cooling output/Number of fan modules
12 kW/4
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,000 mm
To fit enclosure type
TS IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 60 Hz
400 V, 3~, 50 Hz
Rated current max.
At 50 Hz: 7.5 A
Max. cooling output
12 kW
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Inverter-controlled compressor
Start-up current (LRA)
11 A
Pre-fuse
Miniature circuit-breaker/fuse: 20 A
Storage temperature range
-20 °C...50 °C
Operating temperature range
15 °C...35 °C
Noise level
At 50 Hz: 69 dB(A)
Refrigerant/cooling medium
Refrigerant: R410A
Cooling medium: Refrigerant
Protection category to IEC 60 529
IP 20
Packs of
1 pc(s).
Weight/pack
207 kg
Customs tariff number
84195080
EAN
4028177691315
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
SK LCP Rack DX, Refrigerant-based split cooling unit for rack cooling, Mounted on the side of the rack, flush, Cooling of one up to maximum two racks, Support of IT-compatible, #front-to-back# air routing,
Certificates
EAC
Declarations
Declaration of conformity
Data sheets
Graphics
Safety data sheet
Technical Data sheet
Tender text for LCP Rack DX, 3311.410 WHD (mm)
300x2000x1000

LCP Rack DX:

IT-optimised design, providing ideal support for