Fan module for LCP Rack/Inline CW

Article number: SK 3313.016

Increased cooling output. Additionally redundancy can be achieved or the electric power consumption can be reduced.

Article number:
SK 3313.016
Design
for LCP Rack/Inline CW
Product description
To increase the cooling output, individual fan modules may be retro-fitted into the LCPs. Additional integration can also achieve redundancy or reduce the electric power consumption of the LCPs.
Benefits
May be connected with the system operational
Tool-free replacement of the fan modules
Function principle
Installing fan modules in an LCP increases the air throughput and hence the cooling output of the chosen variant. With an adequate cooling output, fan modules may be added to create redundancy. Retro-fitting additional fans over and above the required volumetric air flow allows you to reduce the electrical energy consumption, since the fans then operate at a lower speed. At the same time, the noise level of the unit will be significantly reduced.
Material
Enclosure: Sheet steel
Colour
RAL 9005
Supply includes
1 fan unit
EC fan
Fully wired ready for connection
Assembly parts
Power consumption
500 W
Speed
3,780 rpm
Air throughput (unimpeded air flow)
1,990 m³/h
Packs of
1 pc(s).
Weight/pack
6.9 kg
Customs tariff number
84145915
EAN
4028177954458
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK fan module, UL, for LCP Rack/Inline CW, based on VX IT, to increase the cooling capacity, individual fan modules may be retro-fitted into the LCPs. Additional integration can also achieve redundancy or reduce the electric power consumption of the LCP. RAL 9005
LCP fan module 3313.016,
for LCP CW 3313.130/230/250/260/530/540/550/560/570/238/268/548/538/568
3314.130/230/250/260/530/540/542/550/560/570/238/268/548/538/568

The fan module is suitable for use with LCP Rack / Inline CW.
The installation of additional fan modules in an LCP increases the air
throughput and thus the cooling output of the respective variant.
If the cooling output is already sufficient, additional fan modules may
be used to achieve redundancy.
Furthermore, the electrical power consumption can be reduced by
retrofitting fans capable of supplying more than the required volumetric
air flow, because the fans will then operate at a lower speed.
The noise level of the unit will also be reduced significantly.
The fans can be replaced in a matter of seconds and without the need for
tools or specially qualified personnel, also during continued operation

LCP fan module, supply includes:
Metal housing with EC fan, ready for connection and with fixing
materials
Rated voltage: 200 V-277 V, 1~, N PE, 50/60 Hz
Max. speed: 3780 rpm
Max. power consumption: 500 W
qV (volumetric flow) unimpeded: 1990 m³/h
Colour: RAL 9005