TopTherm Blue e roof-mounted cooling unit Total cooling output 0.50 - 4.00 kW

Article number: SK 3383.540

Energy-efficient Blue e roof-mounted cooling units in output categories from 500 W to 4,000 W with e-Comfort controller integrated as standard and electrical condensate evaporation.

Article number:
SK 3383.540
Product description
Energy-efficient Blue e roof-mounted cooling units with integral e-Comfort controller and electric condensate evaporation as standard.
Benefits
May be linked to the IoT interface via Blue e IoT adaptor for cooling units from 500 W cooling output with e-Comfort controller
Material
Sheet steel
Colour
RAL 7035
Supply includes
Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts
Total cooling output to DIN EN 14511
Cooling output L35 L35/50 Hz: 1 kW
Cooling output L35 L35/60 Hz: 1.09 kW
Cooling output L35 L50/50 Hz: 0.71 kW
Cooling output L35 L50/60 Hz: 0.81 kW
Rated operating voltage
400 V, 2~, 50 Hz/60 Hz
Note
The roof-mounted cooling unit 3273.500 is also suitable for office applications, thanks to its low noise level.
Rated current max.
At 50 Hz: 1.7 A
At 60 Hz: 2.2 A
Start-up current max.
At 50 Hz: 4.6 A
At 60 Hz: 5.7 A
Air throughput (unimpeded air flow)
External circuit: 1,600 m³/h
Internal circuit: 491 m³/h
Energy efficiency ratio (EER) 50/60 Hz L35 L35
Refrigeration factor L35 L35 (EER) 50 Hz: 2.58
Refrigeration factor L35 L35 (EER) 60 Hz: 2.28
Design
roof-mounted
Dimensions
Width: 597 mm
Height: 417 mm
Depth: 475 mm
Protection category to IEC 60 529
External circuit IP 34
Internal circuit IP 54
Refrigerant/cooling medium
Refrigerant: R134a
Quantity: 0.65 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 0.93 t
Type of electrical connection
Plug-in terminal strip
Duty cycle
100 %
Temperature control
e-Comfort controller (factory setting +35 °C)
Operating temperature range
10 °C...55 °C
Storage temperature range
-40 °C...70 °C
Setting range
20 °C...55 °C
Power consumption Pel
Power consumption L35 L35/50 Hz: 0.38 kW
Power consumption L35 L35/60 Hz: 0.45 kW
Power consumption L35 L50/50 Hz: 0.42 kW
Power consumption L35 L50/60 Hz: 0.54 kW
Permissible operating pressure (p. max.)
28 bar
Pre-fuse
Transformer circuit-breaker: 6.3...10 A
Packs of
1 pc(s).
Weight/pack
46 kg
Customs tariff number
84158200
EAN
4028177323223
ETIM 7.0
EC000855
ECLASS 8.0
27180704
Product description
SK cooling unit Blue e, roof-mounted, 1 kW, 400 V, 2~, 50/60 Hz, Sheet steel, WHD: 597 x 417 x 475 mm
Approvals
CSA
UL + C-UL - FTTA
UR + C-UR (recognized)
Certificates
EAC
Declarations
Declaration of conformity
Declaration of conformity - F-gas regulation
Declaration of conformity UK
Documentation
Instructions
Safety instructions
White Paper
Data sheets
Safety data sheet refrigerant
Technical details
Technical system catalogue
3383540
Roof-mounted cooling unit TopTherm Blue e
Energy-efficient Blue e roof-mounted cooling units with integral
e-Comfort controller, hydrophobic RiNano coating on the condenser and e
condensate evaporation as standard.
Total cooling output L35 L35 50/60 Hz: 1,0 / 1,09 kW
Total cooling output L35 L50 50/60 Hz: 0,71 / 0,81 kW
Power consumption L35 L35 50/60 Hz: 0,38 / 0,45 kW
Power consumption L35 L50 50/60 Hz: 0,42 / 0,54 kW
Rated power input 50/60 Hz: 1,7 / 2,2 A
Rated operating voltage: 400 V, 2~, 50/60 Hz
Temperature control: e-comfortcontroller (factory setting +35 °C)
Dimensions [WxHxD]: 597x417x475 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,58 / 2,28
Refrigerant / Quantity: R134a / 650 g
Operating temperature range: 10 °C to 55 °C
Setting range: 20 °C to 55 °C
Protection category IP to IEC 60 529: Internal circuit IP 54, external
circuit IP 34