TopTherm wall-mounted cooling unit Blue e, UL Type 3R/4 0.5 - 2.5 kW

Article number: SK 3329.548

Energy-efficient Blue e wall-mounted cooling units in output categories 500 W to 2,500 W with integral e-Comfort controller and electric condensate evaporation (from 1000 W) as standard, protection category UL Type 3R/4, 12.

Article number:
SK 3329.548
Product description
Energy-efficient Blue e wall-mounted cooling units with integral e-Comfort controller and electric condensate evaporation as standard. Protection category UL Type 3R/4, 12.
Benefits
Suitable for outdoor siting
Blue e technology
May be linked to the IoT interface via Blue e IoT adaptor for cooling units from 500 W cooling output with e-Comfort controller
Material
Sheet steel
Colour
RAL 7035
Supply includes
Condenser with hydrophobic RiNano coating
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts
Integral electric condensate evaporation
Total cooling output to DIN EN 14511
Cooling output L35 L35/50 Hz: 2.55 kW
Cooling output L35 L35/60 Hz: 2.75 kW
Cooling output L35 L50/50 Hz: 1.95 kW
Cooling output L35 L50/60 Hz: 2 kW
Rated operating voltage
400 V, 3~, 50 Hz
460 V, 3~, 60 Hz
Rated current max.
At 50 Hz: 3.3 A
At 60 Hz: 3.4 A
Start-up current max.
At 50 Hz: 6.8 A
At 60 Hz: 7.6 A
Air throughput (unimpeded air flow)
External circuit: 1,200 m³/h
Internal circuit: 1,200 m³/h
Energy efficiency ratio (EER) 50/60 Hz L35 L35
Refrigeration factor L35 L35 (EER) 50 Hz: 2.14
Refrigeration factor L35 L35 (EER) 60 Hz: 1.97
Design
wall-mounted
Dimensions
Width: 405 mm
Height: 1,650 mm
Depth: 388 mm
Protection category to IEC 60 529
External circuit IP 34
Internal circuit IP 56
Protection category NEMA
UL Type 3R
UL Type 4
UL Type 12
Refrigerant/cooling medium
Refrigerant: R134a
Quantity: 0.9 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 1.29 t
Temperature control
e-Comfort controller (factory setting +35 °C)
Operating temperature range
-20 °C...50 °C
Operating temperature
Compressor cooling mode from +10 °C ambient temperature. Only the internal fan is active in the temperature range -20 °C to +10 °C.
Storage temperature range
-40 °C...70 °C
Setting range
20 °C...50 °C
Power consumption Pel
Power consumption L35 L35/50 Hz: 1.19 kW
Power consumption L35 L35/60 Hz: 1.39 kW
Power consumption L35 L50/50 Hz: 1.45 kW
Power consumption L35 L50/60 Hz: 1.75 kW
Permissible operating pressure (p. max.)
28 bar
Pre-fuse
Motor circuit-breaker: 6.3...10 A
Packs of
1 pc(s).
Weight/pack
84 kg
Customs tariff number
84158200
EAN
4028177937116
ETIM 7.0
EC000855
ECLASS 8.0
27180704
Product description
SK cooling unit Blue e, wall-mounted, UL Type 3R/4,, 2.43 kW, 400 V, 3~, 50 Hz, 460 V, 3~, 60 Hz,, Sheet steel,, WHD: 405 x 1650 x 388 mm,
Approvals
UL + C-UL (listed)
UL + C-UL - FTTA
Certificates
EAC
Declarations
Declaration of conformity
Declaration of conformity - F-gas regulation
Declaration of conformity UK
Documentation
Instructions
White Paper
Data sheets
Safety data sheet refrigerant
Technical system catalogue
3329548
Wall-mounted cooling unit TopTherm Blue e, UL Type 3R/4
Energy-efficient Blue e wall-mounted cooling units
with e-Comfort controller integrated as standard,
and electrical condensate evaporation (from 1000 W),
hydrophobic RiNano coating on the condenser,
protection category NEMA 3R/4/12.
Total cooling output L35 L35 50/60 Hz: 2,55 / 2,75 kW
Total cooling output L35 L50 50/60 Hz: 1,95 / 2,0 kW
Power consumption L35 L35 50/60 Hz: 1,19 / 1,39 kW
Power consumption L35 L50 50/60 Hz: 1,45 / 1,75 kW
Rated power input 50/60 Hz: 3,3 / 3,4 A
Rated operating voltage: 400-460 V, 3~, 50/60 Hz
Temperature control: e-Comfortcontroller (factory setting +35 °C)
Dimensions [WxHxD]: 405x1650x388 mm
Installation depth: 440 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,14 / 1,97
Refrigerant / Quantity:R134a / 900 g
Operating temperature range: -20 °C to 50 °C
Setting range: 20 °C to 50 °C
Bearing temperature range: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 56, external
circuit IP 34
Weight: 84 kg
Note: Compressor cooling mode from +10 °C ambient temperature. Only the
internal fan is active in the temperature range -20 °C to +10 °C.