Busbar support PLS

Article number: SV 9341.050

For PLS special busbars 800 A/1600 A, 3-pole and 4-pole, suitable for top-mounting.

Article number:
SV 9341.050
Material
Polyamide
Fire protection corresponding to UL 94-V0
Colour
RAL 7035
Rated operating voltage
1000 V, 3~
1500 V (DC)
Electrical ratings UL (SCCR)
14 kA - 600 V, support spacing 150 mm, PLS 800 busbars
22 kA - 600 V, support spacing 150 mm, PLS 800 busbars
50 kA - 600 V, support spacing 250 mm, PLS 800 busbars, circuit breaker max. 600 A, DIVQ/7
50 kA - 600 V, support spacing 250 mm, PLS 800 busbars, Fuse Class L max. 800 A, JDDZ/7
65 kA - 480 V, support spacing 200 mm, PLS 800 busbars, circuit breaker max. 600 A, DIVQ/7
65 kA - 600 V, support spacing 500 mm, PLS 800 busbars, Fuse Class L max. 800 A, JDDZ/7
Note on Model No.
The use of a base tray is required for UL applications
UL approval only applies in conjunction with AC application
Top-mounting
Yes
Number of poles
3-pole
To fit busbars
PLS 800
Internal attachment
Yes
Centre-to-centre spacing of busbars
60 mm
Packs of
4 pc(s).
Weight/pack
0.368 kg
Customs tariff number
85469010
EAN
4028177525634
ETIM 7.0
EC001166
ECLASS 8.0
27400607
Product description
SV Busbar support, PLS 800, 3-pole, 60 mm bar centre distance, UL design
Approvals
ABS
C-UL
Lloyds Register of Shipping
UL + C-UL (listed)
Declarations
Declaration of conformity
Declaration of conformity UK
Documentation
Further information
Instructions
Safety instructions
Data sheets
General technical information
Short-circuit resistance diagram
Technical details
PLS 800 UL busbar support
PLS 800 UL busbar support
3-pole
Technical specifications
Bar centre distance: 60 mm
Busbars: PLS 800 special busbar
Construction width: 20 mm
Length: 190 mm
Note
The use of the base tray is compulsory for
UL applications.