- Article number:
- SK 3301.800
- Benefits
- Even air distribution in front of the 482.6 mm (19") level
- Applications
- Cooling of IT equipment in IT enclosures sited as stand-alone units in secondary rooms
- Function principle
- The device supports front-to-back air routing typical of IT applications, and regulates the server inlet temperature to the set value
- The hot waste air from the IT equipment is drawn into the device at the rear of the IT enclosure, cooled, and the cooled air blown back in front of the 482.6 mm (19") level
- Material
- Sheet steel
- Colour
- RAL 7035
- Supply includes
- Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Fully wired ready for connection
Drilling template
Air baffle plate
Assembly parts - Total cooling output to DIN EN 14511
- Total cooling output L35 L45: 3,200 W
- Air throughput (unimpeded air flow)
- External circuit: 2,000 m³/h
Internal circuit: 1,450 m³/h - Energy efficiency ratio (EER) 50/60 Hz L35 L35
- Refrigeration factor L35 L35 (EER) 50 Hz: 1.6
- Rated operating voltage
- 230 V, 1~, 50 Hz
- Rated current max.
- At 50 Hz: 10.4 A
- Type of electrical connection
- Plug-in terminal strip
- Dimensions
- Width: 597 mm
Height: 417 mm
Depth: 895 mm - Start-up current max.
- At 50 Hz: 36 A
- Duty cycle
- 100 %
- Temperature control
- Control of the server inlet temperature
- Monitoring
- Monitoring of incoming air temperature
- Permissible operating pressure (p. max.)
- 25 bar
- Pre-fuse
- Miniature circuit-breaker/fuse: 16 A
- Setting range
- 20 °C...25 °C
- Protection category to IEC 60 529
- External circuit IP 20
- Internal circuit IP 20
- Refrigerant/cooling medium
- Refrigerant: R134a
Quantity: 1.2 kg
Global Warming Potential (GWP): 1,430 - Packs of
- 1 pc(s).
- Net weight
- 89 kg
- Gross weight
- 98 kg
- Customs tariff number
- 84158200
- EAN
- 4028177558298
- ETIM 9
- EC000855
- ETIM 8
- EC000855
- ECLASS 8.0
- 27180704
- Product description
- SK Roof-mounted cooling unit, For cooling IT equipment, Control of the server air infeed temperature, WHD: 597x417x895 mm, 230 V, 1~, 50 Hz
IT roof-mounted cooling unit Rittal TopTherm
Model No. 3301.800
The unit supports "front to back" air routing typical of IT
applications, and regulates the server inlet temperature to the set
value. The hot waste air from the IT equipment is drawn into the unit at
the rear of the IT enclosure, cooled, and the cooled air blown back in
front of the 482.6 mm (19") level. It is mounted on the roof of the IT
enclosure, and cools the air volume inside the enclosure. An air baffle
plate for air-routing in front of the 482.6 mm (19") front level is
included with the supply.
Technical specifications of the unit:
Useful cooling output to DIN 3168 L25 L35 3000 W
Rated operating voltage 230 V, 1/50 Hz
Power consumption Pel to DIN 3168, L25, L35, 1820 W
Dimensions W x H x D [mm] 597 x 417 x 895
Refrigerant R 134 a
Setting range of the server inlet temperature +20°C to + 25°C
Factory setting: +35 °C
Ambient temperature range: +20°C to +45°C
Temperature control and monitoring via comfort controller with two
floating fault signal outlets, door limit switch connection and
condensate warning
Connection via plug-in terminal strip
Protection category to EN 60 529/10.91
External circuit IP 20/ Internal circuit IP 20
Weight 96,6 kg
Colour RAL 7035
Model No. 3301.800
The unit supports "front to back" air routing typical of IT
applications, and regulates the server inlet temperature to the set
value. The hot waste air from the IT equipment is drawn into the unit at
the rear of the IT enclosure, cooled, and the cooled air blown back in
front of the 482.6 mm (19") level. It is mounted on the roof of the IT
enclosure, and cools the air volume inside the enclosure. An air baffle
plate for air-routing in front of the 482.6 mm (19") front level is
included with the supply.
Technical specifications of the unit:
Useful cooling output to DIN 3168 L25 L35 3000 W
Rated operating voltage 230 V, 1/50 Hz
Power consumption Pel to DIN 3168, L25, L35, 1820 W
Dimensions W x H x D [mm] 597 x 417 x 895
Refrigerant R 134 a
Setting range of the server inlet temperature +20°C to + 25°C
Factory setting: +35 °C
Ambient temperature range: +20°C to +45°C
Temperature control and monitoring via comfort controller with two
floating fault signal outlets, door limit switch connection and
condensate warning
Connection via plug-in terminal strip
Protection category to EN 60 529/10.91
External circuit IP 20/ Internal circuit IP 20
Weight 96,6 kg
Colour RAL 7035