More on the product
Create PDF of this page+ Product description
Function principle: |
To protect connected equipment Integral test holes provide measurement access to the contact parts of the fuse inserts For cable outlet at the top, the NH fuse-switch disconnector must be mounted on the board rotated through 180° |
---|---|
Material: |
Polyamide Fire protection corresponding to UL 94-V0 Contact tracks: Silver-plated hard copper |
Colour: | RAL 7035 |
Test specification: | IEC/DIN EN 60 947-3 |
For NH size: | 000 |
Rated operating current max.: | 125 A |
Rated operating voltage: |
440 V (DC), 3~ 690 V (AC), 3~ |
Number of poles: | 3-pole |
Cable outlet: | Top/bottom |
Type of electrical connection: | Box terminal |
Connection for round conductor cross-sections: | 2.5 ‐ 50 mm² |
Clamping area for laminated copper bars (W x H): | 10 x 10 mm |
Dimensions: |
Width: 49.5 mm Height: 174.5 mm Depth: 96 mm |
Packs of: | 1 pc(s). |
Weight/pack: | 0.576 kg |
Copper weight (kg per piece): | 0.145 |
Customs tariff number: | 85369095 |
EAN: | 4028177937604 |
ETIM 7.0: | EC001040 |
ECLASS 8.0: | 27371401 |
Product description: | LV HRC fused interrupter, size 000, 690 V (RiLine Compact) |