Micro Data Center Level E

Article number: DK 7999.009

The IT Safe MDC Level E is a small data centre, perfectly tailored to your requirements, with an optimised footprint that expands as your IT develops, and can also be relocated to a different site when necessary.

Article number:
DK 7999.009
Product description
The Micro Data Center Level E (MDC Level E) is a modular security safe with an operator door at the front and service door at the rear. The MDC Level E is supplied with one cable entry in each side element as standard and is available in a range of sizes.
Benefits
Suitable for installation at poorly accessible sites
Expandability for graduated investment in line with IT growth.
Prepared for the installation of various IT climate control solutions
Systems may be dismantled and reassembled, for maximum investment security
Applications
A high level of protection against potential physical threats for IT
Targeted configuration components transform the safe into a complete, compact data centre.
Material
Sheet steel, coated
Colour
Enclosure: RAL 7035
Service door: RAL 7035
Operator door: RAL 7035
Supply includes
Security safe with operator door and servicing door
Cable entry in both side elements
Both doors with key lock
Options
Different lock variants
Different cable entry systems
Cable entry in the top and base unit
Twin-walled doors
Choice of door hinges
Supporting structure
Supporting structure with fire protection
Note
The tests were performed as system tests and confirmed with test reports.
Project planning on request
Protection standards
The safe was tested as a system.
The single safe was tested as a system with one single-leaf door and one bifold door and mechanical lock
Fire resistance class F 90 to DIN 4102 Part 2, compliance with limits ΔT < 50 K, rel. humidity < 85% over 30 minutes
Smoke protection based on DIN 18095-2: 1991-03
Burglar resistance RC 2, tool attack analogous to DIN EN 1630:2011-09
Burglar resistance RC 3 tool attack analogous to DIN EN 1630: 2011-09 (restricted configuration options)
Clearances
Installation height for components: 47 U
Standard protection from
Fire
Extinguishing water
Corrosive gases
Vandalism
Unauthorised access
Dust
Theft/burglary
IP protection category to IEC 60 529
IP 56
Packs of
1 pc(s).
EAN
4028177717084
ETIM 7.0
EC002499
ECLASS 8.0
27180207
Product description
Micro Data Center Level E. The Micro Data Center Level E (MDC Level E) is a modular security safe with an operator door at the front and service door at the rear. The MDC Level E comes with one cable entry in each side element as standard.
Micro Data Center Level E
Item number: 7999.009
IT - SECURITY SAFE
Supply of a modular IT security safe.
Fire protection F 90 tested according to DIN 4102 (ISO time-temperature
curve) but 30 minutes within the limits of 50 K temperature increase and
85% relative humidity. Furthermore, proof of tested burglary protection
RC 2, based on EN 1630, must be provided.
According to EN 60529, the protection class of the housing (at least IP
56) must be fulfilled.
All tests must be carried out as system tests.
The values achieved must be verified with test certificates.
The IT security safe must be of modular, "steel in cassette" design for
free-standing installation.
A demountable, as well as expandable construction must be proven.
Installation around existing, commissioned IT components is required.
Decommissioning of the IT components during installation is not
possible!

The IT security safe must have two security doors, one at the front and
one at the back. These security doors must be equipped with an
appropriate access control system.

The connections of the elements of the IT security safe are to be
designed using form-fit connection techniques that can be released at
any time.

The ingress of extinguishing water and moisture, as well as corrosive
fumes into the modular IT safety safe, must be prevented by design
measures.

Technical features
The following features must be provided:

Housing dimensions outside:
Height: 2210 mm / 2410 mm
Width: 1100 mm (single safe, without attachments)
Width: 2200 mm (linkage of 2 safes, without attachments)
Width: 3300 mm (linkage of 3 safes, without attachments)
Width: 4400 mm (linkage of 4 safes, without attachments)
Depth: 1204 mm / 1404 mm (without attachments)

Housing dimensions inside:
Height: 2030 mm / 2230 mm (42 U / 47 U)
Width: 920 mm (single safe)
Width:1840 mm (linkage of 2 safes)
Width: 2760 mm (linkage of 3 safes)
Width: 3680 mm (linkage of 4 safes)
Depth: 1000 mm / 1200 mm

The IT security safe must have the possibility of stringing together
several safes. The modules arranged in relation to each other must have
large inspection openings for the cabling of the network racks located
in the interior. Test certificates must be provided for the baying of
the safety safes.

The IT security safe must be designed in such a way that it is also
possible to add further modules at a later date.

It must be ensured that the existing network or server rack does not
have to be relocated as part of the expansion, unless the conditions on
site require this.

The expandability of the existing system must be guaranteed for at least
5 years.

The IT security safe must have a cable entry system at several positions
of the safe. The cable duct systems must be designed in an "open
construction", suitable for installation with already installed IT
components. The cable duct systems have to be fireproof, waterproof and
gas-resistant for the introduction of data, control and supply cables
into the modular IT security safe.

A duct material that allows later retrofitting to data and supply lines
is to be used as sealing material.

Cable entry
Standard (this version is already included)
Cable entry arranged in the rear area of the side elements designed as
soft duct
Variant 1
Cable entry arranged in the rear area of the side elements designed as
hard duct
Variant 2a
Cable entry arranged in the head element designed as a hard duct (in
addition to the standard)
Variant 2b
Cable entry arranged in the bottom element designed as a hard duct (in
addition to the standard)
Variant 3
Cable entry arranged in the rear area of the side elements designed as a
cable box

To provide an adapted process climate on the inside of the IT security
safe, a cooling unit in split design must be provided.
The inner and outer circuits are hermetically separated. The evaporator
part must be located on the inside of the IT - safety safe, while the
condenser is placed outside the safe or the building.
Alternatively, a solution with cold water cooling must be provided.

Closure version

Standard (This version is already included)
The locking mechanism is designed as a safety lock with 2 keys each. The
locks of the operator and service door are not keyed alike.

Variant 1
The locking mechanism (operator and/or service door) is designed as an
electronic key combination lock with mechanical revision opening by
means of an emergency key.

Variant 2
The locking mechanism (operator and/or service door) is designed as an
electronic lock which must be controlled by means of an access control
system provided by the customer.

Operator and service door version

Standard (This design is already included in item 1.1)
Door in single-leaf design.

Variant 1
Door in double-leaf design

Burglary protection
Modular security safe with tested burglary protection in accordance with
EN 1627. A system test must be verified.

Standard (This version is already included)
Burglary protection RC 2 in accordance with EN 1630

optional
Burglary protection RC 3 following EN 1630 (reduced configuration)

Errors and technical modifications excepted.