Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

Article number: SK 3313.390

Ideal for cooling of small and medium-sized IT applications.

Article number:
SK 3313.390
Design
DX
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Temperature monitoring and control
With redundant temperature sensor integrated at the air end as standard
Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements
Specific maintenance of the LCP DX due to separation of cooling and server racks
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling.
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
Material
Sheet steel, spray-finished
Colour
RAL 7035
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Design
Suite cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L35: 20 kW
Modulation range
5 ‐ 20 kW
Total cooling output/Number of fan modules
20 kW/4
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 50 Hz/60 Hz
Rated current max.
At 50 Hz: 12.4 A
Max. cooling output
20 kW
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
SNMP card
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Inverter-controlled compressor
Pre-fuse
Miniature circuit-breaker/fuse: 32 A
Operating temperature range
-20 °C...50 °C
Noise level
At 50 Hz: 68 dB(A)
Protection category to IEC 60 529
IP 20
Packs of
1 pc(s).
Weight/pack
239 kg
Customs tariff number
84195080
EAN
4028177953826
ETIM 8
EC002515
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
LCP Inline DX, 20 kW, flush, RAL 7035, WHD: 300 x 2000 x 1200 mm, 380 – 480 V/3~/50 – 60 Hz
Declarations
Declaration of conformity
Documentation
Instructions
Data sheets
Graphics
Technical Data sheet
LCP Inline DX, 3313.390
WHD (mm) 300x2000x1200 mm

IT-optimised design, providing ideal support for "front-to-back" air
routing for the 482.6 mm (19") installations.

As a direct expansion, the integrated air/refrigerant heat exchanger
guarantees a cooling output of up to 20 kW with standard server
enclosure dimensions, the lowest possible weight, and comprehensive
possibilities for monitoring.
The LCP Inline DX is mounted on the side of the rack.
The warm server air is drawn in through a perforated rear door and the
cooled air is blown back via a perforated door in front of the
perforated doors of the server rack and is thus made available to the
482.6 mm (19") equipment once more.
The LCP Inline DX is closed up to the server rack at the front and rear
and there forms a flush joint with the rack.

The unit is equipped with four EC fans, for maximum efficiency and
minimum power consumption.
The flow characteristics of the heat exchanger are optimised for the
lowest possible pressure losses on the air side. This minimises the
energy consumption of the fans.

An integrated inverter with corresponding controller serves to regulate
the speed of the installed compressor
This permits stepless adaptation of the output, also in partial-load
operation, and by reducing energy consumption also achieves a reduction
in operating costs.

Alongside the compressor, the cooling circuit of the LCP Inline DX
comprises a liquid receiver, electronic expansion valve, optimised heat
exchanger, high and low-pressure sensors, Schrader valves, filter dryer,
non-return valve, high/low-pressure switch and shut-off devices.
The refrigerant connections and the electrical power connection to the
unit can be realised from above or below.
The system comprising LCP Inline DX and external condenser must be
filled with refrigerant R410A after installation at the site.

The LCP Inline DX and the server rack remain separate from each other.
This simplifies assembly and service work and excludes the need for
unwanted access to the server rack for maintenance purposes.
Maintenance and service for all relevant components can be realised
quickly and simply thanks to the optimised layout. The fans can be
exchanged quickly and at any time, even while the system is operational
(hot swapping).
The fans are installed in the cold air section, which increases their
service life.
.
Condensate management is integrated into the unit. Any condensate is
collected in a collecting tray in the base and from there discharged to
the outside via a hose.

Thanks to the integrated controller, the LCP Inline DX operates fully
autonomously.
The setpoint is the server intake air temperature, which is
automatically held constant at the set value.
Three sensors are present in each case for detection of the cold and
warm air temperatures, providing for the appropriate redundancy.

Monitoring and alarm management for all physical parameters is realised
via SNMP and Ethernet.
The SNMP card is integrated as standard in the electrical box, already
connected to the main board.

A display with operating keys is integrated on the front of the unit to
display and set the physical parameters.

The external condenser is needed to operate the LCP Inline DX and has to
be ordered separately.
Installation and commissioning on site, laying of the refrigerant pipes,
and evacuation and filling of the system with refrigerant are not
included in the scope of supply and must be realised by correspondingly
qualified persons.

Technical specifications:
Useful cooling output:
20 kW at 35 °C ambient temperature at place of installation of the
condenser
Installed fans: 4
Air throughput: max. 4.800 m³/h
Intake temperature, set: 22 °C
Connection, liquid side: 12 mm
Connection, gas discharge side: 12 mm
Piping, LCP DX to condenser (liquid/gas): 12 / 16mm
Power supply:,,400 V, 3~, N, PE, 50/ 60 Hz (voltage range 380-480 V)
Prefuse: 32A
Max. connected load: 7,9kW
Refrigerant: R410A
Connection length, max.: 45 m
Height difference (condenser higher/lower), max: 20/3 m
Dimensions (WxHxD): 300x2000x1200mm
Weight: 239 kg
Colour: RAL 7035
Integrated SNMP card for network connection

Option on application:
Humidifier
Dehumidification + heater
Air filter (G3) with monitoring
Condensate pump
High temperature condenser (up to +53°C)
Low temperature condenser + winter kit (down to -40°C)

Needed accessories:
3311.363,,
Air cooled condenser for 3313.390 (-20°C to +45°C)