Product details
Basic protection or high availability protection for data centres. Whether you are planning a new building or an extension to your data centre, we are at your side with decades of experience.
More on the product
Create PDF of this page+ Product description
Design: | High Availability room |
---|---|
Product description: | The basic protection room - an optimum, modular room-within-a-room solution for protecting IT/infrastructure components. The High Availability room - certified maximum physical protection for data centres and IT system locations. |
Note: | Tested products are tested as a complete construction. This comprises the cellular structure and installation modules such as doors, cable shields or ventilation units. By contrast, component testing only refers to individual parts. |
Corrosive fire gases: | Protection from acrid gases to DIN 18 095 |
Falling debris: |
Shock test as system test, 3 shocks of 200 kg from 1.5 m after 45 minutes flame impingement time Shock test as system test, 1 shock of 200 kg from 1.5 m after 30 minutes flame impingement time |
Dust-tightness: | IP 5x as system testing to EN 60 529, for the cellular structure and its built-in modules |
EMC protection: | Protection against high-frequency irradiation and radiation, verified by tests on comparable components by TU Aachen |
Fire protection: |
ECB·S certifications to EN 1047-2, 50 K temperature increase and 85% rel. humidity up to 24 hours (reheating period), 60 minutes flame impingement time F120 as system test, according to the limits of EN 1363 (DIN 4102), for the cellular structure and its built-in modules |
Unauthorised access: |
RC 3 as system test to EN 1627/1630, for the cellular structure and its built-in modules, such as doors RC 4 only as component testing to EN 1627/DIN 1630, door system only |
Water: |
Standing water, 72 hours, 40 cm, maximum 20 drops Extinguisher water, IP x6 as system testing to IEC 60 529, for the cellular structure and its built-in modules Relative humidity, 85%, over 24 hours (reheat period), 60 minutes flame impingement time, to EN 1047-2 Relative humidity, 85%, over 30 minutes |
Explosion protection : | Detonation test as system testing of 200 kg TNT from 40 m |
Packs of: | 1 pc(s). |
EAN: | 4028177689350 |
ETIM 7.0: | EC002499 |
ECLASS 8.0: | 27180207 |
Product description: | RM Security room, High Availability room (HVR) |