Liquid Cooling Package LCP Inline CW, LCP Inline CWG

Model No. 3313.550

  Product Lifecycle  
Limited
  • Liquid Cooling Package LCP Inline CW, LCP Inline CWG

    Discontinued article.

    Information on the discontinued articles
    Product expires on 31.10.2023
    This item is being replaced by 3314550
    Liquid Cooling Package LCP Inline CW/CWG
     

    Close
    Product details

    Bayed climate control designed for siting within a bayed enclosure suite. The hot air is extracted at the rear of the unit, cooled and then expelled forwards to the cold aisle.

    + Product description

    Design: CWG
    Benefits: Maximum energy efficiency due to EC fan technology and IT-based control
    Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
    Optimum adaptability due to dynamic, continuous control of the cold water volume flow
    By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
    Targeted cooling output due to modular fan units
    Fan modules configurable as n+1 redundancy
    Standard 3-phase connection for electrical redundancy
    With redundant temperature sensor integrated at the air end as standard
    The separation of cooling and enclosure prevents the ingress of water into the server enclosure
    A footprint of max. 0.36 m² for all cooling services
    Improved heat recovery, thanks to high water return temperatures when using LCP CW glycol variants, for example in combination with a heat pump
    Optimum access for maintenance and servicing from the front and rear
    Tool-free replacement of the fan modules
    Function principle: The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
    Material: Sheet steel, spray-finished
    Colour: RAL 7035
    Options: Direct connection of additional CMC III sensors is supported
    Racks 2200 mm high
    Design: Suite cooling
    Monitoring: Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
    Direct connection of the unit via SNMP over Ethernet
    Integration into RiZone
    Total cooling output/Number of fan modules: 20 kW/2
    31 kW/3
    35 kW/4
    Air throughput (unimpeded air flow): At 50 Hz: 5,000 m³/h
    Number of fans: 2
    Dimensions: Width: 300 mm
    Height: 2,000 mm
    Depth: 1,200 mm
    To fit enclosure type: VX IT
    Installation in bayed enclosure suite: Flush
    Rated operating voltage: 230 V, 1~, 50 Hz/60 Hz
    400 V, 3~, 50 Hz/60 Hz
    Max. cooling output: 28 kW
    Type of electrical connection: Connector
    Duty cycle: 100 %
    Cooling medium: Water/glycol
    EC fan: yes
    Fans may be exchanged with the system operational: yes
    Temperature control: Linear fan control
    Two-way control valve
    Water connections: DN 40 (G 1½" external thread)
    Permissible operating pressure (p. max.): 10 bar
    Water inlet temperature: 15 °C
    Protection category to IEC 60 529: IP 20
    Optimized condensate management even at low water flow temperatures: yes
    Packs of: 1 pc(s).
    Weight/pack: 280 kg
    Customs tariff number: 84158200
    EAN: 4028177953932
    ETIM 7.0: EC002515
    ECLASS 8.0: 27180712
    Product description: SK LCP Inline CW/glycol, 28 kW, RAL 7035, WHD: 300 x 2000 x 1200 mm

    + Approvals

    Declerations:
    Declaration of conformity: 
    CS DE, EN

    + Downloads / CAD

    Data Sheets:
    Visio Shapes: 
    DE
    Documentation:
    Instructions: 
    CS DE EN

    + Add accessories

     Liquid Cooling Package LCP Inline CW, LCP Inline CWG

    Model No.

    Close
    +
    [X] Close

    Required 

    $nbsp;

    Product data (ZIP)

    Rittal does not assume any liability for the topicality of the data downloaded locally on your device.

     I agree

    Close