Liquid Cooling Package LCP Inline CW, LCP Inline CWG

Model No. 3313.568

  Product Lifecycle  
Passive
  • Liquid Cooling Package LCP Inline CW, LCP Inline CWG
  • Liquid Cooling Package LCP Inline CW, LCP Inline CWG
    Product details

    Bayed climate control designed for siting within a bayed enclosure suite. The hot air is extracted at the rear of the unit, cooled and then expelled forwards to the cold aisle.

    + Product description

    Design: CW
    Benefits: Maximum energy efficiency due to EC fan technology and IT-based control
    Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
    Optimum adaptability due to dynamic, continuous control of the cold water volume flow
    By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
    Targeted cooling output due to modular fan units
    Fan modules configurable as n+1 redundancy
    With redundant temperature sensor integrated at the air end as standard
    The separation of cooling and enclosure prevents the ingress of water into the server enclosure
    A footprint of max. 0.36 m² for all cooling services
    Optimum access for maintenance and servicing from the front and rear
    Tool-free replacement of the fan modules
    Function principle: The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
    Material: Sheet steel, spray-finished
    Surface finish: RAL 9005, finely textured matt
    Colour: RAL 9005
    Options: Direct connection of additional CMC III sensors is supported
    Racks 2200 mm high
    Design: Suite cooling
    Monitoring: Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
    Direct connection of the unit via SNMP over Ethernet
    Integration into RiZone
    Total cooling output/Number of fan modules: 48 kW/4
    51 kW/5
    53 kW/6
    Air throughput (unimpeded air flow): At 60 Hz: 8,000 m³/h
    Number of fans: 6
    Dimensions: Width: 300 mm
    Height: 2,000 mm
    Depth: 1,200 mm
    To fit enclosure type: VX IT
    TS IT PRO
    Installation in bayed enclosure suite: Set forward
    Rated operating voltage: 200 V - 240 V, 1~, 50 Hz/60 Hz
    200 – 240 V AC
    Max. cooling output: 53 kW
    Type of electrical connection: Connector
    Duty cycle: 100 %
    Cooling medium: Water
    : Water quality according to unit specifications.
    EC fan: yes
    Fans may be exchanged with the system operational: yes
    Temperature control: Linear fan control
    Two-way control valve
    Water connections: DN 40 (G 1½" external thread)
    Permissible operating pressure (p. max.): 10 bar
    Water inlet temperature: 15 °C
    Protection category to IEC 60 529: IP 20
    Packs of: 1 pc(s).
    Weight/pack: 260 kg
    Customs tariff number: 84195080
    EAN: 4028177962774
    ETIM 7.0: EC002515
    ECLASS 8.0: 27180712
    Product description: SK LCP Inline CW UL, set forward, based on VX IT, air/water heat exchanger for suite cooling, side mounting on the rack, set forward by 200 mm, RAL 9005

    + Approvals

    Approvals:
    UR + C-UR (recognized): 
    EN

    + Downloads / CAD

    Data Sheets:
    Visio Shapes: 
    DE
    Documentation:
    Instructions: 
    CS DE EN FR

    + Add accessories

    + Tender texts

    LCP Inline CW UL, Protruding, 3313.568:
    Regulatory model no.: LCP N 7A3P63SC9D000

    The design of the unit is optimised for use in data centres. The
    integrated air/water heat exchanger guarantees a sensitive cooling
    output of 53 kW with standard server enclosure dimensions, the lowest
    possible weight and comprehensive possibilities for monitoring.

    The air/water heat exchanger is mounted on the side of the rack.
    The LCP Inline extracts the hot air from the servers via a vented rear
    door.
    The unit is set forward from the front of the server rack by approx. 200
    mm and returns cooled air to the 19" equipment by blowing it in front of
    the vented doors of the server rack from the left and right.
    The use of 6 integrated EC fan modules (cooling output up to 53 kW,
    180844 BTU/h) achieves maximum efficiency.

    The air/water heat exchanger and server rack are incorporated into a
    single bayed suite, but nevertheless remain separate from each other.
    This eliminates the risk of water penetrating into the server rack and
    simplifies installation and service.
    There is no access to the adjacent IT rack via the LCP.
    Leakage monitoring is integrated. If a sensor installed in the
    condensate tray detects a leakage, the main controller issues an alarm
    message and/or interrupts the supply of cooling medium to the unit.
    All components in the condensate area are made of stainless steel to
    prevent corrosion

    The unit was developed for the exclusive purpose of providing a
    sensitive cooling output.
    An accessory kit enables the water connection to be realised either at
    the top or at the bottom (G 1½" external thread).
    Fast commissioning of the unit thanks to fast and simple air bleeding.
    The fans can be replaced in a matter of seconds and without the need for
    tools or specially qualified personnel, also during continued operation.

    An advanced software concept enabling network integration for the
    monitoring/setting of all technical parameters is implemented as a
    standard feature.
    An integrated fail-safe operating mode maintains reliable cooling in
    case of a controller failure.
    Up to eight additional sensors (temperature/humidity, etc.) can be
    connected.

    Technical data:
    Sensitive cooling output with 4/5/6 fans: 48/51/53 kW
    Operating temperature range, ambient: 10 °C - 50 °C
    Operating temperature range, cooling medium: 10 °C - 30 °C
    (non-condensing)
    Lower inlet temperatures possible after consultation with the
    manufacturer.

    Installed fans: 6 (max. 6 possible)
    Air throughput: 8,000 m³/h (6 fans)
    Cooling output (six fans): 53 kW (180844 BTU/h)
    Air intake temperature: 24 °C
    Water inlet temperature: 15 °C
    Medium: Water (or water/glycol mixture)
    Cooling medium throughput (0-140 l/min): approx. 125 l/min (pure water)
    Pressure loss: approx. 1 bar
    Water connection: G 1½" external thread
    Voltage: 1~ 200-240V, AC50/60Hz, L1, (L2/N), PE
    Max. connected load (6 fan modules): 3150 W
    Control according to server air intake temperature, realised by way of
    throughput regulation and EC fans with infinitely variable speed
    Noise level at a distance of 1 m: max. 88 dB(A)
    Colour:
    Housing frame, roof plate, side panels and rear door: RAL 9005
    Dimensions: WxHxD: 300 x 2000 x 1200 mm
    Weight as delivered: approx. 260 kg

    Controller/interfaces:
    Network port (RJ 45): Ethernet to IEEE 802.3 via 10/100BaseT with PoE
    Front USB port: Mini USB for system setup
    Rear USB port: For USB thumb drive for data memory up to 32 GB
    Front SD-HC slot: Data memory up to 32 GB
    Alarm relay output: Changeover contact for extra-low voltage (24 V DC, 1
    A)
    Digital inputs: 2x (terminal)
    Protocols, Ethernet:
    TCP/IPv4, TCP/IPv6, SNMPv1, SNMPv2c, SNMPv3, Modbus TCP, OPC ua, Telnet,
    SSH, (S)FTP, HTTP (S), NTP, DHCP, DNS, SMTP (S), Syslog
    Eight additional sensors (temperature, humidity, etc.) can be connected

    Software
    Control according to server air intake temperature
    Automatic or manual control can be selected
    Remote control via SNMP, Modbus TCP, OPC ua is possible
    Target value specification by way of an external temperature sensor
    Water-side ?T control can be selected for efficient chiller operation
    Programming of logic operations (tasks) is possible in order to automate
    specific processes.

    Touch screen display, color, installed
    The display shows the user all relevant operating parameters directly on
    the LCP.
    This has the advantage of being able to see the status of the device
    briefly and at a glance, and to react as quickly as possible if
    necessary.

    The following parameters can be read in different levels:

    Display of the supplied cold air temperature to the 19" equipment.
    Display of the discharged warm air temperature from the 19" equipment
    Cooling capacity
    Cooling water supply/return temperature
    Cooling water flow rate
    Position of the control valve
    Overview of all parameters at a glance
    Display of alarm and warning messages
    Overview page with IP address of the device, software version and
    contact person (can be entered individually)
    Change of the setpoint of the cold air temperature before the 19" level
    can be done on the display (locking possible if not desired)
    4,3" display, 480 x 272 pixel
    Resistive touch
    type. 280 cd/m²
    Operating temperature: -20°C to +70°C
    Connecting cable

    Special features:
    Simple maintenance of the unit from the front and back, enabling cable
    channels and aisle containment to be positioned above the unit.
    Tool-free fan replacement without interrupting operation
    Available installation height of the adjacent server rack: free
    (standard: 42 U)

    Optional:
    Fan module to increase cooling output: 3313.016
    Connection hose, bottom/top: 3311.040
    Condensate pump: 3312.012 (only for supply voltage 230-240 V)
    Rear adaptor for LCP CW Inline, Protruding, 3313.530/560/570: 3312.081
    Integrated droplet separator on request