More on the product
Create PDF of this page– Recommended accessories
+ Product description
Benefits: |
The perfect symbiosis of the VX25 baying enclosure system and Blue e+ cooling unit The cooling unit is easily pulled out forwards for maintenance purposes No assembly work required – the cooling unit, door-operated switch and connection cabling are installed ready-to-connect Cooling unit offers all the benefits of Blue e+ Technology |
---|---|
Material: | Sheet steel |
Colour: | RAL 7035 |
Supply includes: |
Basic enclosure VX25, door, roof, rear panel, side panels, gland plates, mounting plate Lock: 3 mm double-bit Integral door-operated switch Integral Blue e+ cooling unit Electric condensate evaporator Pleated filter Condensate hose (3 m) |
Options: | For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages. |
Total cooling output to DIN EN 14511: |
Cooling output L35 L35/50 Hz: 1.3 kW Cooling output L35 L35/60 Hz: 1.3 kW Cooling output L35 L50/50 Hz: 0.76 kW Cooling output L35 L50/60 Hz: 0.76 kW |
Rated operating voltage: |
110 V - 240 V, 1~, 50 Hz/60 Hz 380 V - 480 V, 3~, 50 Hz/60 Hz |
Note: |
Operation without a pleated filter is inadmissible By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions. |
Rated power input: | 0,75 kW |
Energy efficiency ratio (EER) 50/60 Hz L35 L35: |
Refrigeration factor L35 L35 (EER) 50 Hz: 2.04 Refrigeration factor L35 L35 (EER) 60 Hz: 2.04 |
Seasonal energy efficiency ratio (SEER) 50/60 Hz: | 5,3 |
Design: | Integrated |
Dimensions: |
Width: 800 mm Height: 2,200 mm Depth: 600 mm |
Protection category to IEC 60 529: |
External circuit IP 54 with pleated filter Internal circuit IP 54 with pleated filter |
Refrigerant/cooling medium: |
Refrigerant: R134a Quantity: 0.59 kg Global Warming Potential (GWP): 1,430 CO₂ equivalent (CO₂e): 0.85 t |
Temperature control: | e+ controller (factory setting +35 °C) |
Operating temperature range: | -20 °C...55 °C |
Storage temperature range: | -40 °C...70 °C |
Operating temperature range of refrigerant circuit (active): | -20 °C...45 °C |
Heat pipe operating temperature range: | 3 °C...60 °C |
Setting range: | 20 °C...50 °C |
Power consumption Pel: |
Power consumption L35 L35/50 Hz: 0.67 kW Power consumption L35 L35/60 Hz: 0.67 kW Power consumption L35 L50/50 Hz: 0.68 kW Power consumption L35 L50/60 Hz: 0.68 kW |
Permissible operating pressure (p. max.): | 24 bar |
Packs of: | 1 pc(s). |
Weight/pack: | 180 kg |
Customs tariff number: | 94032080 |
EAN: | 4028177927148 |
ETIM 7.0: | EC000855 |
ECLASS 8.0: | 27180704 |
Product description: | SK VX25 Blue e+ Integration solution,, Sheet steel,, cooling module, 1.3 kW,, 110-240 V, 1~, 50/60 Hz, 380-480 V, 3~, 50/60 Hz, WHD: 800 x 2200 x 600 mm |
+ Approvals
Certificates: |
EAC:
RU
|
---|---|
Declerations: |
+ Add accessories
+ Tender texts
3185.030
SK VX25 Blue e+ integration solution
The perfect symbiosis of the VX25 baying enclosure system and Blue e+
cooling unit, The cooling unit is easily pulled out forwards for
maintenance purposes, No assembly work required – the cooling unit,
door-operated switch and connection cabling are installed
ready-to-connect, Cooling unit offers all the benefits of Blue e+
Technology
Total cooling output L35 L35 50/60 Hz: 1,3 / 1,3 kW
Total cooling output L35 L50 50/60 Hz: 0,76 / 0,76 kW
Power consumption L35 L35 50/60 Hz: 0,67 / 0,67 kW
Power consumption L35 L50 50/60 Hz: 0,61 / 0,61 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions: [WxHxD]:
Enclosure: 800x2200x600 mm
Mounting plate: 699x1696 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,04
Refrigeration factor (SEER) 50/60 Hz: 5,3
Refrigeration / Quantity: R134a / 590 g
Operating temperature: -20 °C to 55 °C
Setting range: 20 °C to 50 °C
Storage temperature: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 54 with
pleated filter, External circuit IP 54 with pleated filter
Weight: 180 kg
SK VX25 Blue e+ integration solution
The perfect symbiosis of the VX25 baying enclosure system and Blue e+
cooling unit, The cooling unit is easily pulled out forwards for
maintenance purposes, No assembly work required – the cooling unit,
door-operated switch and connection cabling are installed
ready-to-connect, Cooling unit offers all the benefits of Blue e+
Technology
Total cooling output L35 L35 50/60 Hz: 1,3 / 1,3 kW
Total cooling output L35 L50 50/60 Hz: 0,76 / 0,76 kW
Power consumption L35 L35 50/60 Hz: 0,67 / 0,67 kW
Power consumption L35 L50 50/60 Hz: 0,61 / 0,61 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions: [WxHxD]:
Enclosure: 800x2200x600 mm
Mounting plate: 699x1696 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,04
Refrigeration factor (SEER) 50/60 Hz: 5,3
Refrigeration / Quantity: R134a / 590 g
Operating temperature: -20 °C to 55 °C
Setting range: 20 °C to 50 °C
Storage temperature: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 54 with
pleated filter, External circuit IP 54 with pleated filter
Weight: 180 kg