More on the product
Create PDF of this page+ Product description
Product description: | EMC fan-and-filter units offer a high shielding/attenuation effect and meet requirement category 2 to EN 61587-3. |
---|---|
Colour: | RAL 7035 |
Supply includes: | Complete unit ready to install, including chopped-fibre filter mat |
Fan: | Axial, shaded pole motor |
Air throughput (unimpeded air flow): |
At 50 Hz: 100 m³/h At 60 Hz: 115 m³/h |
Air throughput with outlet filter including chopped-fibre filter mat (quantity x order number): |
1 x 3239060: 74/87 m³/h 2 x 3239060: 84/98 m³/h |
Rated operating voltage: | 230 V, 1~, 50 Hz/60 Hz |
Rated current max.: |
At 50 Hz: 0.12 A At 60 Hz: 0.09 A |
Power consumption Pel: |
At 50 Hz: 15 W At 60 Hz: 14 W |
Dimensions: |
Width: 204 mm Height: 204 mm |
Installation dimensions: |
Build depth: 24 mm Installation depth: 90 mm |
Mounting cut-out: |
Cut-out width: 177 mm Cut-out height: 177 mm |
EMC version: | yes |
Note: | To improve energy efficiency and extend the service life of the devices, we recommend the use of thermostats or temperature displays |
IP protection category to IEC 60 529: |
IP54 with chopped-fibre filter IP56 with chopped-fibre filter and hose-proof hood |
Protection category NEMA: |
Type 12 with chopped-fibre filter Type 3, 3R, 4, 4X with chopped-fibre filter and hose-proof hood |
Pre-fuse: | Miniature circuit-breaker/fuse: 2 A |
Service life of fans (L10, 40 °C): |
At 50 Hz: 68,200 h At 60 Hz: 68,200 h |
Operating temperature range: | -15 °C...55 °C |
Storage temperature range: | -30 °C...70 °C |
Noise level: |
At 50 Hz: 46 dB(A) At 60 Hz: 49 dB(A) |
Packs of: | 1 pc(s). |
Weight/pack: | 1,2 kg |
Customs tariff number: | 84145915 |
EAN: | 4028177652446 |
ETIM 7.0: | EC000320 |
ECLASS 8.0: | 27180716 |
Product description: | SK Fan-and-filter unit TopTherm, 100/115 m³/h, 230 V, 1~, 50/60 Hz, WHD: 204 x 204 x 24 mm, EMC |
+ Approvals
Approvals: | |
---|---|
Declerations: |
+ Add accessories
+ Tender texts
EMC fan-and-filter units offer a high shielding/attenuation effect and
meet requirement category 2 to EN 61587-3.
Air troughput (unimpeded air flow): 100 / 115 m3/h
Power consumption 50/60 Hz: 19 / 18 W
Rated power input 50/60 Hz: 0,12 / 0,11 A
Rated operating voltage: 230 V, 1~, 50/60 Hz
Diagonal fan: Axial, shaded pole motor
Dimensions [WxH]: 204x204 mm
Installation depth: 90 mm
Build depth: 24 mm
Required mounting cut-out [WxH]: 177x177 mm
Operating temperature range: -15°C to +55°C
Storage temperature range: -30°C to +70°C
Colour: RAL 7035
Protection category IP to IEC 60 529:
IP 54 with fleece filter
IP 56 with fleece filter with hose-proof hood
Protection category NEMA:
Type 12 with fleece filter
Type 3, 3R, 4, 4X with fleece filter with hose-proof hood
Noise level 50/60 Hz: 46 / 49 dB(A)
Service life 50/60 Hz: 68.200 / 68.200 h
Weight: 1,2 kg
meet requirement category 2 to EN 61587-3.
Air troughput (unimpeded air flow): 100 / 115 m3/h
Power consumption 50/60 Hz: 19 / 18 W
Rated power input 50/60 Hz: 0,12 / 0,11 A
Rated operating voltage: 230 V, 1~, 50/60 Hz
Diagonal fan: Axial, shaded pole motor
Dimensions [WxH]: 204x204 mm
Installation depth: 90 mm
Build depth: 24 mm
Required mounting cut-out [WxH]: 177x177 mm
Operating temperature range: -15°C to +55°C
Storage temperature range: -30°C to +70°C
Colour: RAL 7035
Protection category IP to IEC 60 529:
IP 54 with fleece filter
IP 56 with fleece filter with hose-proof hood
Protection category NEMA:
Type 12 with fleece filter
Type 3, 3R, 4, 4X with fleece filter with hose-proof hood
Noise level 50/60 Hz: 46 / 49 dB(A)
Service life 50/60 Hz: 68.200 / 68.200 h
Weight: 1,2 kg