  • RiMatrix S Standard room
  • RiMatrix S Standard room
    Product details

    The standardised data centre is assembled at your premises within the context of hot aisle / cold aisle containment.

    + Product description

    Product description: The standardised data centre is assembled at your premises within the context of hot aisle / cold aisle containment.
    Benefits: Enhanced energy efficiency
    Aisle containment is a combination of door and roof components which allow consistent separation of the hot and cold air
    Supply includes: Advice and ROI calculation
    Delivery and integration into the customer infrastructure
    Commissioning and handover
    Documentation, training and instruction
    Hotline and service/service agreements
    Precise-fit aisle containment
    Clearance depth: 7,000 mm
    Clearance height: 2,722 mm
    Clearance width: 4,774 mm
    Climate control (ZUCS): 180 kW + 20 kW
    n+2 redundant
    Number of low-voltage main distributors: 2
    No. of PDU Basic: 36
    Serverracks (600x2000x1200mm): 16
    Combined network/server rack (800 x 2000 x 1200 mm): 2
    Design burglar protection: yes
    Humidification and dehumidification system: optional
    Room extinguisher system: optional
    Version: Double 9
    Dimensions: Width: 4,839 mm
    Height: 2,750 mm
    Depth: 7,070 mm
    Packs of: 1 pc(s).
    Customs tariff number: 73089059
    EAN: 4028177702523
    ETIM 7.0: EC002499
    ECLASS 8.0: 27180207
    Product description: DK RiMatrix S Standard room, Double 9

    + Downloads / CAD

    + Tender texts

    Standard data centre 180kW, 16+2 racks,
    including cooling, for installation in a standard room ,,
    ,,,,,,
    Fully functional data centre comprising 2 rack
    suites (depth 1200 mm) with 8 server racks and a
    network rack each, installed in a fully enclosed
    housing.

    The standard data centre is enclosed by a complete
    housing of double-panelled, foamed wall and roof
    elements with a total thickness of 30 mm.
    The 600 mm wide hot aisle is partitioned within the
    standard room and provided with a sliding door.
    The cold aisle is 1200 mm wide and connects to the
    access area on the air side.

    The standard data centre incorporates a fully
    functional raised-floor construction, with air intake
    and outlet grilles in the form of dip-galvanised
    gratings.

    Air-circulating cooling units (CRAC systems) are
    installed in the cavity space of the raised floor. The
    CRAC systems do not occupy space within the rack (Zero
    U-Space Cooling Systems).
    A CRAC system is installed under each server rack.
    Each CRAC system offers a nominal cooling output of 12
    kW; the average heat load capacity per rack is thus
    10.5 kW, taking into account n+2 redundancy over the
    total number of CRAC systems. The intake temperature
    for cooling is 20°C, observing temperature limit
    values according to ASHRAE 2008 (max. 27°C) within the
    cold aisle.

    The cooled intake air is blown into the cold aisle by
    EC fans under the floor gratings. Flat filter fleeces
    are fitted between the fan grilles and the floor
    gratings to filter the circulating air.


    The intake temperature and speed of the EC fans are
    regulated by a controller in the standard data centre,
    which communicates with the controller of an optional
    chiller station via a system bus for purposes of
    energy efficiency optimisation. The controller is not
    accommodated in the IT racks and thus does not occupy
    rack installation space.

    The standard data centre is equipped ready for use
    with a cold piping system comprising polypropylene
    piping; the individual heat exchangers are connected
    by way of high-pressure hoses.

    Required chiller set provided by the customer:
    The standard data centre must be equipped with a
    straight ball valve to regulate the air intake
    temperature to the target value, a flowmeter and two
    temperature sensors to measure the coolant flow volume
    and the feed and return temperatures, as well as to
    calculate the heat output.

    Required chiller set must be supplied:
    The standard data centre must be supplied without ball
    valve and sensors for the coolant.
    The volume of the medium is regulated by the
    variable-speed pump of the chiller station of the
    standard data centre; the sensors are fitted in the
    chiller station.
    ,,,,,,,,,,
    The standard data centre incorporates switchgear with
    fused feeders for the installed rack suite. The
    switchgear spreads the feeders over two panels to
    establish an A/B power supply.

    From the switchgear, the distribution busbars of the
    individual racks are wired ready for use and comprise
    Power Distribution Units with 24 C13 and 6 C19
    sockets. Each rack is provided with two PDUs to
    establish an A/B power supply.

    The power supply is routed above the racks. The data
    cables are routed to the IT racks separately from the
    power supply cables. The installation of the data
    cables is to be performed by the site
    operator/customer.

    Lighting and service socket are protected by way of an
    RCCB. Emergency lighting is installed.

    The standard data centre is equipped with an early
    fire detection system. To this end, air is drawn from
    the raised floor of the hot aisle via a perforated
    plastic pipe. The alarm is given by a monitoring
    system with Web access and SNMP interface.

    The standard data centre is installed and commissioned
    ready for use (with the exception of data cabling),
    including installation of the operating power supply
    and cooling system.

    Standard data centre version with 16+2 racks for a
    standard room
    ,,

    Outside dimensions,,Inside dimensions,,
    Length:,,7060 mm,,Length:,,7000 mm,,
    Width:,,4840 mm,,Width:,,4780 mm,,
    Height:,,2740 mm,,Height:,,2710 mm,,
    ,,,,
    Walls without door require an assembly clearance of
    100 mm to the building walls. The roof of the
    enclosures requires an assembly clearance of 200 mm to
    the building ceiling.
    ,,


     RiMatrix S Standard room