Liquid Cooling Package LCP Inline CW, LCP Inline CWG

Model No. SK 3313.570

  Product Lifecycle  
New
  • Liquid Cooling Package LCP Inline CW, LCP Inline CWG
    Product details

    Bayed climate control designed for siting within a bayed enclosure suite. The hot air is extracted at the rear of the unit, cooled and then expelled forwards to the cold aisle.

    Not available off the shelf, please contact your sales representative.

    + Product description

    Benefits: Maximum energy efficiency due to EC fan technology and IT-based control
    Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
    Optimum adaptability due to dynamic, continuous control of the cold water volume flow
    By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
    Targeted cooling output due to modular fan units
    Fan modules configurable as n+1 redundancy
    Standard 3-phase connection for electrical redundancy
    With redundant temperature sensor integrated at the air end as standard
    The separation of cooling and enclosure prevents the ingress of water into the server enclosure
    A footprint of max. 0.36 m² for all cooling services
    Improved heat recovery, thanks to high water return temperatures when using LCP CW glycol variants, for example in combination with a heat pump
    Optimum access for maintenance and servicing from the front and rear
    Tool-free replacement of the fan modules
    Function principle: The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
    IT monitoring: Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
    Direct connection of the unit via SNMP over Ethernet
    Integration into RiZone
    Material: Sheet steel, spray-finished
    Colour: RAL 7035
    Protection category IP to IEC 60 529: IP 20
    Options: Direct connection of additional CMC III sensors is supported
    Racks 2200 mm high
    Variant: Suite cooling
    Total cooling output/Number of fan modules: 38 kW / 4 
    40 kW / 5 
    44 kW / 6 
    Number of fan modules in supplied state: 4
    Total cooling output: 35 kW
    Air throughput (unimpeded air flow): At 50 Hz: 4800 m³/h
    Rated operating voltage: 230 V, 1~, 50 Hz/60 Hz
    400 V, 3~, 50 Hz/60 Hz
    Dimensions: Width: 300 mm
    Height: 2000 mm
    Depth: 1200 mm
    Temperature control: Linear fan control
    Two-way control valve
    To fit: VX IT
    Installation in bayed enclosure suite: Set forward
    Temperature range: Water inlet: +15 °C
    Refrigerant/cooling medium: Cooling medium: Water/glycol
    Type of electrical connection: Connector
    Duty cycle: 100 %
    Design: CWG
    Permissible operating pressure (p. max.): 10 bar
    EC fan: yes
    Fans may be exchanged with the system operational: yes
    Water connections: DN 40 (G 1½" external thread)
    Optimised condensate management, even at low water inlet temperatures: yes
    eCl@ss 8.0/8.1: 27180712
    Packs of: 1 pc(s).
    Weight/pack: 280 kg
    EAN: 4028177953956
    Customs tariff number: 84158200
    ETIM 7.0: EC002515
    ETIM 6.0: EC002515
    eCl@ss 8.0/8.1: 27180712
    eCl@ss 6.0/6.1: 27180712
    Product description: SK LCP Inline CW/glycol, 35 kW, RAL 7035, WHD: 300 x 2000 x 1200 mm

    + Approvals

    Declarations:
    Declaration of conformity: 
    (EN, DE)

    + Downloads

    Drivers/software:
    MIB: 
    (Global)

    + Add accessories


     
     
     
     
     
     
     

     Liquid Cooling Package LCP Inline CW, LCP Inline CWG

    Model No. SK 3313.570

    Close
    +
    [X] Close

    Required 

    $nbsp;

    Product data (ZIP)

    Rittal does not assume any liability for the topicality of the data downloaded locally on your device.

     I agree

    Close