Circuit-breaker component adaptor 3-pole

Model No. 9342.400

  Product Lifecycle  
Active
  • Circuit-breaker component adaptor 3-pole
    Product details

    Circuit-breaker adaptor for universal, simplified assembly of circuit-breakers.

    + Product description

    Material: Polyamide
    Fire protection corresponding to UL 94-V0
    Colour: RAL 7035
    Type of electrical connection: Box terminal
    Rated current max.: 100 A
    Rated operating voltage: 690 V, 3~
    Electrical ratings UL (SCCR): 65 kA - 480 V, Manual Motor Controller max. 100 A, NLRV/7
    Cable outlet: Top
    For bar systems with centre-to-centre spacing: 60 mm
    Note: Cable outlet: Switch outlet or as outgoing cable from the switchgear
    The technical data may vary for UL applications
    Number of poles: 3-pole
    For universal switchgear application: yes
    Dimensions: Width: 72 mm
    Height: 210 mm
    Connection for round conductor cross-sections: 10 ‐ 35 mm²
    Clamping area for laminated copper bars (W x H): 10 x 7.8 mm
    To fit busbars: Height: 5, 10 mm
    To fit manufacturer (model): ABB (MS 495, MS 496, MS 497)
    Eaton (PKZ2)
    Schneider Electric (GV3ME80)
    Siemens (S3)
    Packs of: 1 pc(s).
    Weight/pack: 0,58 kg
    Copper weight (kg per piece): 0.114
    Customs tariff number: 85369095
    EAN: 4028177503694
    ETIM 7.0: EC001531
    ECLASS 8.0: 27370304
    Product description: SV Circuit-breaker component adaptor, 100 A, 690 V, 3-pole, cable outlet top, round conductor connection 10-35 mm², clamping area WH: 10x7,8 mm

    + Approvals

    Approvals:
    ABS: 
    EN
    C-UL: 
    EN
    DNV-GL: 
    EN
    Lloyds Register of Shipping: 
    EN
    UL + C-UL (listed): 
    EN
    Declerations:
    Declaration of conformity: 
    DE
    Declaration of conformity UK: 
    EN

    + Downloads / CAD

    Data Sheets:
    General technical information: 
    CS DA DE EN ES FI FR HU IT NL NO PL RU SV TR ZH
    Short-circuit resistance diagram: 
    DE EN
    Technical details: 
    CS DA DE EN ES FI FR HU IT NL NO PL RU SV TR ZH
    Documentation:
    Instructions: 
    DE, EN, FR
    Safety instructions: 
    Global

    + Add accessories

    + Tender texts

    Circuit-breaker component adaptor up to 100 A
    CB component adaptor up to 100 A, 3 pole,
    cable outlet at the top
    for busbar thickness 5/10 mm and PLS 800/1600
    Type of connection
    Connection clamp: Box terminal
    Round conductor: 10 - 35 qmm
    Clamping area for laminated copper bar:
    10 x 7.8 mm
    For UL applications: AWG 2-6
    Technical specifications
    Construction width: 72 mm
    Length: 210 mm
    Electrical parameters
    For IEC applications:
    Rated current: up to 100 A
    Rated operating voltage Ue: AC 690 V
    For UL applications:
    Rated current: up to 100 A
    Rated operating voltage Ue: AC 600 V
    System:
    Rittal RiLine60

     Circuit-breaker component adaptor 3-pole

    Model No.