PSM measurement modules with CAN bus for PSM busbars

Model No. DK 7859.420

  Product Lifecycle  
Active
  • PSM measurement modules with CAN bus for PSM busbars
    Product details

    PSM measurement modules with switching functions for outputs and energy measurement. Versions with IEC 60320 C13 & C19 slots and CEE 7/3 (earthing contact socket) available.

    + Also required

    + Product description

    Description: A power meter and switching functions for the output slots can be added to any PSM busbar with these PSM plug-in modules. The modules are also suitable for upgrading existing PSM installations if it becomes necessary to record the power data or add a switching option for the connected equipment. There are three variants available with different socket types. In the PSM busbar, the PSM modules occupy two module slots each. Measurements are displayed locally on a backlit LC display. For quick checks, the colour changes to red if current and power limits are exceeded.
    Benefits: Simple, shock-hazard-protected, plug & play installation with the system operational
    PSM module is easily fitted into and removed from the PSM busbar, allowing it to be used at changing locations
    Compatible with the European PSM busbar range
    CAN bus for direct connection to CMC III system (RJ 45, 2 x socket)
    In redundant systems, the circuit may be switched over by rotating the module
    Suitable for use at ambient temperatures of up to +60 °C
    Facilitates the implementation of requirements to ISO 50001 and EN 50600-2-2
    Function principle: Measurement of power consumption per module
    Output slots may be switched individually and in groups via CMC III
    Status LEDs for CAN bus communication per module
    LC matrix display with multi-coloured backlight for local display
    Location sensor for correct display and Web view in 90° increments
    Adjustable limits for voltage, current and active power
    Configurable overload detection per module
    High level of measurement accuracy
    Alarm signalling via the display
    Universal connector lock, IEC 60320, C13 and C19 slots that are not needed may be closed
    Measurement functions: Voltage V, current A, frequency Hz
    Active power kW, active energy kWh
    Reactive power kVar, reactive energy kVarh
    Apparent power kVA, apparent energy kVAh
    Power factor cosPhi, crest factor
    Operating hours meter d, h, min
    Measurement accuracy of ± 1%
    Resettable measurement functions / reset via software / interval measurement: Active energy kWh, operating hours meter h, threshold values (voltage, current, power) freely configurable
    Material: Socket inserts: Plastic (PA6 GF 30 V1)
    Section: Aluminium, anodised
    Protection category IP to IEC 60 529: IP 20
    Standards: EN 50 600-2-2
    EN 60950
    Directives: Low Voltage Directive 2014/35/EU
    EMC Directive 2014/30/EU
    Supply includes: PSM measurement modules with CAN bus
    CAN bus connection cable, 1 m
    Sockets: 2 x C13 / 4 x C19 
    Required number of module slots: 2
    Monitoring: Alarm management via CMC III (e.g. e-mail or text message)
    Visualisation of the switching status on the CMC III website and RiZone
    Up to 16 PSM modules on one CMC III PU (per IP address)
    Rights management via CMC III (e.g. restriction of the switching function)
    Dimensions: Width: 53 mm
    Depth: 45 mm
    Length: 500 mm
    Rated operating voltage: 18 V (DC) - 24 V (DC) Power supply via CMC III system 
    Infeeds: Qty.: 1
    Input voltage: 230 V AC
    Tolerance of input voltage: ± 10 %
    Rated voltage: 16 A
    Heat loss per module (at 230 V): 3680 W
    Relay: Type: Dual coil, bistable
    Switching load: 4000 VA
    Interface bus system: 2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
    2 x RJ45 (connection to CMC)
    Maximum quantity of: CMC III Processing Unit: 16
    CMC III Processing Unit Compact: 4
    Ambient conditions: Operating temperature: +5 °C...+60 °C
    Storage temperature: -20 °C...+70 °C
    Relative humidity (non-condensing): 10 %
    Ambient humidity (non-condensing): 90 %
    Maximum operating altitude: 2000 m
    Contamination level: 2
    Interfaces: Network protocol: Network functionality (only in conjunction with CMC III system): IPv4, IPv6, SNMPv3, Modbus/TCP, OPC-UA
    Packs of: 1 pc(s).
    Weight/pack: 0.99 kg
    EAN: 4028177801851
    Customs tariff number: 85369001
    ETIM 7.0: EC000330
    ETIM 6.0: EC000330
    eCl@ss 8.0/8.1: 27371306
    eCl@ss 6.0/6.1: 27142604
    Product description: DK PSM measuring module, for modular PSM power distribution. Occupies 2 slots in the busbar. Output: IEC 60 320 4 x C19, 2 x C13, input: 207 V – 250 V, 16 A, (max. 3680 W)

    + Approvals

    Certificates:
    EAC: 
    (RU)
    Declarations:
    Declaration of conformity: 
    (CS)

    + Downloads

    Data sheets:
    Technical system catalogue:  
    DE   EN  
    Documentation:
    Instructions: 
    (FR, EN, DE)
    Safety instructions: 
    (Global)

    + Add accessories

     Customers who interested in this item also interested in


     
     
     
     
     
     
     

     PSM measurement modules with CAN bus for PSM busbars

    Model No. DK 7859.420

    Close
    +
    [X] Close

    Required 

    $nbsp;

    Product data (ZIP)

    Rittal does not assume any liability for the topicality of the data downloaded locally on your device.

     I agree

    Close