Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

Article number: SK 3311.450

Ideal for cooling of small and medium-sized IT applications.

Article number:
SK 3311.450
Design
LCP Inline DX
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Temperature monitoring and control
With redundant temperature sensor integrated at the air end as standard
Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements
Specific maintenance of the LCP DX due to separation of cooling and server racks
Using LCP DX/FC variants in combination with indirect free cooling helps to save operating costs
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling.
The LCP DX/FC variants include both a refrigerant and a water/glycol heat exchanger. There is an additional free cooler integrated into the external condenser.
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
Material
Sheet steel, spray-finished
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Design
Suite cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L30: 30 kW
Modulation range
8 ‐ 35 kW
Total cooling output/Number of fan modules
35 kW/3
Air throughput (unimpeded air flow)
At 50 Hz: 9,900 m³/h
Dimensions
Width: 600 mm
Height: 2,000 mm
Depth: 1,000 mm
To fit enclosure type
TS IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
360 V, 3~, 50 Hz
480 V, 3~, 60 Hz
Rated current max.
At 50 Hz: 22.4 A
Max. cooling output
35 kW
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
SNMP card
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Inverter-controlled compressor
Pre-fuse
Miniature circuit-breaker/fuse: 40 A
Operating temperature range
15 °C...35 °C
Noise level
At 50 Hz: 69 dB(A)
Protection category to IEC 60 529
IP 20
Packs of
1 pc(s).
Weight/pack
398 kg
Customs tariff number
84158200
EAN
4028177691353
ETIM 8
EC002515
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
Evaporator unit for room cooling in conjunction with condenser 3311.360, width: 300 mm
Certificates
EAC
Declarations
Declaration of conformity
Documentation
Instructions
Data sheets
Graphics
Safety data sheet
Technical Data sheet