TopTherm Filter Fan Units with EC technology

Article number: SK 3245.500

Energy-efficient design of the RTT filter fans with EC technology. From 105.94 cfm with integrated control interface (0-10 V / PWM input and tachometer output signal) for controlling and monitoring the fan.

Article number:
SK 3245.500
Product description
Energy-efficient version of the TopTherm filter fans with diagonal fan technology. Fan 3240.50x to 3245.51x may be controlled and monitored. The fan may be activated via the control interface with tacho signal output integrated as standard. Also, monitoring of the fan speed and function is supported.
Color
RAL 7035
Supply includes
Complete unit ready to install, including fleece filter mat
Fan
Diagonal, EC motor
Unimpeded air flow (with fleece filter)
At 50 Hz: 890 m³/h
At 60 Hz: 890 m³/h
( At 50 Hz: 523.8 cfm
At 60 Hz: 523.8 cfm )
Unimpeded air flow (with folded filter)
At 50 Hz: 1,125 m³/h
At 60 Hz: 1,125 m³/h
( At 50 Hz: 662.15 cfm
At 60 Hz: 662.15 cfm )
Air throughput with outlet filter incl. fleece filter mat (quantity x order number)
1 x 3243200: 630 m³/h
2 x 3243200: 770 m³/h
Rated operating voltage
200 V - 240 V, 1~, 50 Hz/60 Hz
Rated power Pel
At 50 Hz: 165 W
At 60 Hz: 165 W
Rated current max.
At 50 Hz: 1.33 A
At 60 Hz: 1.33 A
Dimensions
Width: 323 mm
Height: 323 mm
( Width: 12.7 ˝
Height: 12.7 ˝ )
Installation depth
130.5 mm
( 5.14 ˝ )
Mounting cut-out
Width of opening: 292 mm
Cut-out height: 292 mm
( Width of opening: 11.5 ˝
Cut-out height: 11.5 ˝ )
Protection category IP to IEC 60 529
IP51 with fleece filter/folded filter
IP52 with folded filter and absorber mat
IP56 with fleece filter/folded filter and hose-proof hood
Protection category NEMA
Type 1, 12, 3, 3R with fleece filter/folded filter and hose-proof hood
Control interface
Yes
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Note
A folded filter can optionally be used to increase the air throughput (see characteristic curve). This can be used with both the filter & roof-mounted fans and the exhaust filters.
For even more efficient operation or for monitoring the fan-and-filter units, we recommend the use of a speed control EC for EC fan-and-filter unit (from air flow rates of 180 m³/h).
Operating temperature range
-25 °C...55 °C
( -13 °F...131 °F )
Storage temperature range
-25 °C...70 °C
( -13 °F...158 °F )
Noise pressure level
At 50 Hz: 72 dB(A)
At 60 Hz: 72 dB(A)
Weight/packaging unit
3.46 kg
( 7.6 lb. )
Packaging unit
1 pc(s).
Customs tariff number
84145915
EAN
4028177652262
ETIM 7.0
EC000320
ECLASS 8.0
27180716
Product description
SK Fan-and-filter unit TopTherm, 523.8 cfm 200-240 V, 1~, 50/60 Hz, WHD: 323 x 323 x 25 mm, EC technology
Approvals
CSA
UL + C-UL - FTTA
UR + C-UR (recognized)
Declarations
Declaration of conformity
Declaration of conformity UK
Documentation
Instructions
Data sheets
Technical System Catalogue
Technical details

You're three steps away from the right air conditioning solution

With the Climate Control QuickFinder you can quickly and easily find the right air conditioning solution for your requirements. Receive the result conveniently by e-mail.