Connection Adapters

Article number: SV 9342.250

For busbar systems with 60 mm center-to-center distance.

Article number:
SV 9342.250
Material
Cover: ABS
Punched section: Polyamide
Fire protection corresponding to UL 94-V0
Color
RAL 7035
Rated current max.
250 A
Rated operating voltage
690 V, 3~
Electrical UL ratings (SCCR)
50 kA - 600 V, fuse class K5 max. 250 A, JDDZ/7
50 kA - 600 V, Combination Motor Controller max. 250 A, NKJH/7
65 kA - 480 V, circuit breaker max. 250 A, DIVQ/7
65 kA - 600 V, fuse class J max. 400 A, JDDZ/7
Cable outlet
Top/bottom
For bar systems with center-to-center spacing
60 mm
Note
The technical data may vary for UL applications.
UL approval only applies in conjunction with AC application
The rated operating voltage for DC applications depends on the busbar arrangement in the busbar support 9340.050/9341.050/9342.050.
Number of poles
3-pole
Dimensions
Width: 90 mm
Height: 210 mm
( Width: 3.54 ˝
Height: 8.27 ˝ )
Clamping area for laminated copper bars (W x H)
18.5 x 15.5 mm
( 0.73 x 0.61 ˝ )
Connection of round conductors, fine wire with wire end ferrule
35 ‐ 120 mm²
Connection of round conductors, multi-wire
35 ‐ 120 mm²
Suitable for busbars
Height: 5, 10 mm
( Height: 0.2, 0.39 ˝ )
Packaging unit
1 pc(s).
Weight/packaging unit
0.78 kg
( 1.7 lb. )
Copper weight (kg per piece)
0.166
Customs tariff number
85369010
EAN
4028177503632
ETIM 7.0
EC001531
ECLASS 8.0
27370304
Product description
SV Connection adaptor, 250 A, 690 V, 3-pole, cable outet top/bottom, round conductor connection 35-120 mm², clamping area WH: 18,5x15,5 mm
Approvals
ABS
C-UL
DNV-GL
Lloyds Register of Shipping
UL + C-UL (listed)
Declarations
Declaration of conformity
Declaration of conformity UK
Documentation
Instructions
Safety instructions
Data sheets
General technical information
Short-circuit resistance diagram
Technical details