Liquid Cooling Package LCP Rack CW, LCP Rack CWG

Article number: SK 3313.238

Cooling via high-performance compact impellers. The LCP draws in air from the side at the rear of the server enclosure and blows the cooled air back into the front part of the server enclosure from the side.

Article number:
SK 3313.238
Version
CW
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimizes the power consumption of the fans
Control of the server inlet temperature
Redundant temperature sensor integrated at the air end
Optimum adaptability due to dynamic, continuous control of the cold water volume flow
By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
Targeted cooling output thanks to modular fan units
Fan modules configurable as n+1 redundancy.
The separation of cooling and enclosure prevents water from entering the server enclosure
A maximum floor area of 0.36 m² for all cooling services
Improved heat recovery due to high water return temperatures when using the LCP CW glycol variants, for example in conjunction with a heat pump
Optimum access for maintenance and service from the front and the rear
Tool-free fan module replacement
Function principle
The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
Material
Carbon steel, spray finished
Surface finish
RAL 9005, fine structure matt
Color
RAL 9005
Options
Fully integrated fire detection and extinguisher system
Automatic server enclosure door opening
Direct connection of additional CMC III sensors is also possible
Racks 2200 mm high
Version
Rack cooling
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage.
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Total cooling output
102030
( 34,12168,243102,364 )
Total cooling output/number of fan modules
10 kW/1
20 kW/2
30 kW/3
( 34,121 BTU/h
68,243 BTU/h
102,364 BTU/h )
Air throughput (unimpeded air flow)
At 60 Hz: 6,500 m³/h
( At 60 Hz: 3,825.8 cfm )
Number of fan modules in supplied state
4
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
( Width: 11.8 ˝
Height: 78.7 ˝
Depth: 47.2 ˝ )
Suitable for enclosure type
VX IT
TS IT PRO
Installation in bayed enclosure suite
Flush
Rated operating voltage
200 V - 240 V, 1~, 50 Hz/60 Hz
200 - 240 V AC
Max. cooling output
30 kW
( 102,364 BTU/h )
Type of connection (electrical)
Connector
Duty cycle
100 %
Cooling medium
Water
Temperature control
Infinitely variable fan control
2-way control ball valve
Water connections
DN 40 (G 1½" external thread)
Permissible operating pressure (p. max.)
10 bar
( 145 PSI )
Water inlet temperature
15 °C
( 59 °F )
Protection category IP to EN 60 529
IP 20
Options
Fully integrated fire detection and extinguisher system
Automatic server enclosure door opening
Direct connection of additional CMC III sensors is also possible
Racks 2200 mm high
Packaging unit
1 pc(s).
Weight/packaging unit
230 kg
( 507.1 lb. )
Customs tariff number
84186900
EAN
4028177962781
ETIM 8
EC002515
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
SK LCP Rack CW UL, RAL 9005, base VX IT, air/water heat exchanger for rack cooling, side mounting on rack, flush
Approvals
UR + C-UR (recognized)
Declarations
Declaration of conformity
Documentation
Instructions
Data sheets
Visio Shapes