Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

Article number: SK 3311.460

Ideal for cooling small and medium-sized IT applications.

Article number:
SK 3311.460
Version
LCP Inline DX/FC
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimizes the power consumption of the fans
Temperature monitoring and control.
Redundant temperature sensor integrated at the air end
Due to the speed-regulated compressor, the cooling output adapts to the actual requirements
Special maintenance of the LCP DX due to separation of cooling and server enclosures
Using LCP DX/FC variants in combination with indirect free cooling helps to save operating costs
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
LCP for use within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling
The LCP DX/FC versions contain both refrigerant as well as a water/glycol heat exchanger. A free cooler is also integrated in the external condenser.
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
Material
Carbon steel, spray finished
Options
Humidifier
Dehumidification and reheater
Condensate lift pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Version
Row Cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L30: 35 kW
Modulation range
8 ‐ 35 kW
Total cooling output/number of fan modules
35 kW/3
( 119,425 BTU/h )
Air throughput (unimpeded air flow)
At 50 Hz: 9,900 m³/h
( At 50 Hz: 5,826.9 cfm )
Dimensions
Width: 600 mm
Height: 2,000 mm
Depth: 1,000 mm
( Width: 23.6 ˝
Height: 78.7 ˝
Depth: 39.4 ˝ )
Suitable for enclosure type
TS IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 60 Hz
400 V, 3~, 50 Hz
Rated current max.
At 50 Hz: 31.6 A
Max. cooling output
35 kW
( 119,425 BTU/h )
Type of connection (electrical)
Connection clamp
Duty cycle
100 %
Cooling medium
Water/glycol
EC fan
Yes
SNMP card
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Infinitely variable fan control
Inverter-controlled compressor
Pre-fuse
Miniature circuit-breaker/fuse: 40 A
Operating temperature range
15 °C...35 °C
( 59 °F...95 °F )
Noise pressure level
At 50 Hz: 69 dB(A)
Protection category IP to EN 60 529
IP 40
Packaging unit
1 pc(s).
Weight/packaging unit
398 kg
( 877.4 lb. )
Customs tariff number
84158200
EAN
4028177691360
ETIM 8
EC002515
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
SK LCP Rack DX, WHD: 600x2000x1000 mm, 119425 BTU/h
Declarations
Declaration of conformity
Documentation
Instructions
Data sheets
Drawings
Safety data sheet
Technical Data sheet