Fire alarm and extinguisher system DET-AC III Master

Article number: DK 7338.121

Compact fire alarm and active extinguisher system with smoke extraction system with 1RU space. For security safes and sealed server racks applications.

Article number:
DK 7338.121
Product description
The active extinguisher system includes the smoke extraction system and the extinguisher unit. The smoke extraction system is identical to that used in the EFD III. When a main alarm is triggered, the extinguishing process starts automatically. For the extinguishing process, the tank is pressurized via a propellant cartridge. The extinguisher gas Novec™ 1230 evaporates at the extinguisher nozzle and is distributed in the server enclosure.
Benefits
Early fire detection
Automatic extinguishing
Innovative extinguisher gas Novec™ 1230: eco-friendly, uncritical for IT components, non-conductive
19" rack mount with just 1 U
Tested by VdS Schadenverhütung GmbH
CAN-Bus Interface to CMC III monitoring system
Floating relay outputs (pre-alarm/main alarm/collective fault)
Technical specifications
Extinguisher gas discharged by propellant gas cartridge, with integrated electrical trigger unit
Integrated extinguisher monitoring (indication of > 15% loss)
Material
Carbon steel
Color
Housing: RAL 7035
Front: RAL 9005
Extinguisher gas
Type: Novec™ 1230
Fill volume: 1.8 l
Tank
Material: Aluminum
Volume: 2 l
Interfaces
4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
1 x/1 x input for door contact switch (terminal/RJ12 jack)
2 x CAN connections for master-slave networking
2 x connection (external alarm/manual triggering device)
1 x voltage output for DET-AC slave III (24 V DC max. 500 mA)
1 x USB
2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
Uninterruptible mains electricity operation
approx. 4 hrs
Note
The system has been designed exclusively for use in closed, non-walk-in enclosure systems with a maximum volume of 2.8 m³.
Display
Plain language display with 6 LEDs
Sensors
Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
Optical smoke detector, top hat rail (sensitivity: approx. 0.25%/m light obscuration)
Dimensions
Width: 482.6 mm
Height: 44 mm
Depth: 660 mm
( Width: 19 ˝
Height: 1.73 ˝
Depth: 26 ˝ )
Operating temperature range
10 °C...40 °C
( 50 °F...104 °F )
Storage temperature range
-20 °C...65 °C
( -4 °F...149 °F )
Storage temperature range, batteries
-15 °C...40 °C
Relative humidity (non-condensing)
96 %
Rated operating voltage
100 V - 240 V, 1~, 50 Hz/60 Hz
Air flow monitoring
approx. ±10% of total air flow
Packaging unit
1 pc(s).
Weight/packaging unit
21.5 kg
( 47.4 lb. )
Customs tariff number
84248970
EAN
4028177699311
ETIM 7.0
EC002685
ECLASS 8.0
40040104
Product description
DK DET-AC III Master, fire detection and extinguishing system, active smoke extraction system, early fire detection, automatic extinguishing.
Certificates
VDS
Declarations
Declaration of conformity