RiLineX NH fuse-switch disconnector

Članak br.: RX 9363.035

RiLineX NH fuse-switch disconnector in size 00 for mounting plates. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Box terminal connection to connect round conductors ranging from min. 1.5 to max. 95 mm². Includes electronic fuse monitoring.

Članak br.:
RX 9363.035
Design
For mounting plate assembly
Benefits
Cover: can be locked and prepared for a lead seal
Voltage test through separate opening
Tool-free changeover of the cable outlet
Park position for simpler maintenance work
All variants also available with electronic fuse monitoring
Material
Polyamide (PA 6)
Fire protection corresponding to UL 94
Contact tracks: Electrolytic copper, silver-plated
Colour
RAL 9005
RAL 35745
Supply includes
Connectors for electronic fuse monitoring
for mounting plate assembly
Da
Cable outlet
Top/bottom
Type of electrical connection
Box terminal
Rated insulation voltage
1.000 kV
Rated operating current max.
160 A
Rated operating voltage
690 V AC
For NH size
00
Test specification
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (fuse inserts)
Dimensions
Width: 106 mm
Height: 229 mm
Depth: 84 mm
Connection of round conductors
1.5 ‐ 16 mm²
Operating temperature range
-5 °C...35 °C
Storage temperature range
-25 °C...70 °C
Number of poles
3-pole
Utilisation category
AC-23B (400 V/100 A)
AC-22B (500 V/100 A)
null
DC-22B (250 V/100 A)
Contamination level
3
with electronic fuse monitoring
Da
IP protection category to IEC 60 529
IP 2XB
Connection of round conductors, fine wire without wire end ferrule
1.5 ‐ 95 mm²
Connection of round conductors, fine wire with wire end ferrule
1.5 ‐ 95 mm²
Power dissipation (max.)
16 W
Packs of
1 pc(s).
Net weight
0,885 kg
Gross weight
0,962 kg
Copper weight (kg per piece)
0,268
Customs tariff number
85369095
ETIM 9
EC001040
Product description
RX NH fuse-switch disconnector size 00, 160 A, 3-pole, box terminal with fuse monitoring 800 V, mounting plate assembly
Izjave
Declaration of conformity
Dokumentacija
Instructions
Quick guide
Safety instructions
Liste podataka
General technical information