Early fire detection system EFD III

Model No. 7338.221

  Product Lifecycle  
Active
  • Early fire detection system EFD III
    Product details

    The EFD system is a compact 482.6 mm (19"), 1 U early fire detection system with active smoke extraction system.

    + Also required

    + Product description

    Product description: The EFD III early fire detection system includes the smoke extraction system in a 482.6 mm (19") subrack with just 1 U. An integral fan continuously extracts air from the area being protected via a system of pipes. The air drawn in passes two fire detectors. If smoke is detected, the highly sensitive detector will emit a pre-alarm, while the second detector will activate the main alarm. The fire detectors are permanently monitored for correct functioning by the evaluation and control electronics on the control card.
    Benefits: Early fire detection
    482.6 mm (19") rack mount with just 1 U
    Tested by VdS Schadenverhütung GmbH
    CAN bus interface to the CMC III monitoring system
    Floating relay outputs (pre-alarm/main alarm/collective fault)
    Material: Sheet steel
    Colour: Enclosure: RAL 7035
    Front: RAL 9005
    Interfaces: 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
    1 x/1 x input for door contact switch (terminal/RJ12 jack)
    2 x CAN connections for master-slave networking
    3 x connection (external alarm/manual call point/tank and fill level)
    1 x voltage output for DET-AC slave III (24 V DC max. 500 mA)
    1 x USB
    2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
    Uninterruptible mains electricity operation: approx. 4 h
    Note: This system is designed solely for use in closed, non-accessible enclosure systems.
    Display: Plain-language display with 6 LEDs
    Sensors: Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
    Optical smoke detector HS (sensitivity: approx. 0.25%/m light obscuration)
    Dimensions: Width: 482.6 mm
    Height: 44 mm
    Depth: 490 mm
    Operating temperature range: 10 °C...40 °C
    Storage temperature range: -20 °C...65 °C
    Storage temperature range of batteries: -15 °C...40 °C
    Relative humidity (non-condensing): 96 %
    Rated operating voltage: 100 V - 240 V, 1~, 50 Hz/60 Hz
    Air flow monitoring: approx. ±10% of total airflow
    Packs of: 1 pc(s).
    Weight/pack: 15 kg
    Customs tariff number: 85311095
    EAN: 4028177699328
    ETIM 7.0: EC002685
    ECLASS 8.0: 40040104
    Product description: DK EFD III, Early fire detection including smoke extraction system, Designed solely for use in closed, non-accessible enclosure systems, 482.6 mm (19") rack mount, 1 U

    + Approvals

    Approvals:
    GOST: 
    RU
    Certificates:
    EAC: 
    RU
    VDS: 
    DE, EN
    Declerations:
    Declaration of conformity: 
    DE, EN

    + Downloads / CAD

    Data Sheets:
    Technical details: 
    DE PL
    Visio Shapes: 
    DE, EN
    Documentation:
    Instructions: 
    DE ES FR Global IT

    + Add accessories

    + Tender texts

    EFD III early fire detection system

    The early fire detection system is able to detect fires at an early
    stage. The compact system occupies 1 U of rack space and is designed for
    installation in the 19" level of closed server enclosure systems.
    An integrated fan continuously draws in air from the protected space via
    a pipe system. This air passes two smoke detectors. If smoke aerosols
    are detected, the high-sensitivity smoke detector triggers a pre-alarm
    state. The second smoke detector triggers the main alarm. The proper
    functioning of the smoke detectors is monitored continuously by the
    evaluation and control electronics on the control board.

    Alarms and fault messages can be output and forwarded to a higher-level
    system (monitoring or control system) via floating contacts.
    An integrated CAN bus interface enables direct connection to the CMC III
    system.
    As an option, the early fire detection system offers a possibility to
    control an external extinguishing agent tank. When the second fire alarm
    threshold is reached, the relay output "Main alarm" and the output for
    the external extinguishing agent tank are triggered.

    Technical data

    Width: 482.6 mm (19")
    Height: 44 mm (1 U)
    Depth: 490 mm
    Housing material: Sheet steel
    Weight: approx. 9.6 kg
    Rated voltage: 100-240 V AC, 50/60 Hz
    Emergency power supply: approx. 4 h
    Max. permissible active current: 1.0 A at 24 V (the sum of all connected
    devices must not exceed the permissible active current of 1.0 A)
    Max. permissible charging current: 350 mA at 24 V

    Ambient temperature:
    +10 °C to +40 °C (operation),
    -20 °C to +65 °C (storage without batteries),
    -15 °C to +40 °C (battery storage)
    Humidity: up to 96% (relative), non-condensing
    Protection category: IP 30

    Connections:
    Terminal for relay output "Pre-alarm", "Fire alarm", "Extinguishing"
    Terminal for relay output "Collective fault"
    Terminal for door contact switch
    Socket (RJ 12) for connection of door contact switch
    3x sockets (RJ 12) for signal outputs "Fault", "Pre-alarm", "Main alarm"
    2x CAN connection for system networking
    Connection for external alarm device
    Connection for external filling level monitoring and control of an
    external tank, max. 500 mA
    Connector for manual alarm
    Voltage supply (UB), max. 500 mA
    USB port
    CAN bus interface to CMC III

    Displays:
    1 plain-language display for status messages
    1 LED green, "Operation"
    1 LED yellow, "Shutdown"
    1 LED red, "Extinguishing system primed"
    1 LED red, "Extinguishing system activated"
    1 LED yellow, "Blocked"
    1 LED yellow, "Fault"

    Sensors (2 different scattered-light sensors for 2 alarm thresholds):
    Optical smoke detector
    (sensitivity: approx. 3.5%/m obscuration)
    Optical smoke detector HS
    (sensitivity: approx. 0.25%/m obscuration)
    Air flow monitoring: approx. +/-10% of overall air flow
    External devices:
    Connection for manual alarm
    Connection for door contact
    Connection for external alarm device
    CAN bus interface to Rittal CMC III

    Model No.: 7338.221
    Manufacturer: Rittal GmbH & Co. KG

     Early fire detection system EFD III

    Model No.

    Close
    +
    [X] Close

    Required 

    $nbsp;

    Product data (ZIP)

    Rittal does not assume any liability for the topicality of the data downloaded locally on your device.

     I agree

    Close