- Статья №.:
- RX 9361315
- Преимущества
- Mounting on the busbar system and cable connection with just one screw
- Материал
- Полиамид (PA 6)
Негорючесть согласно UL 94
- Цвет
- RAL 9005
- Rated current (guideline value, IEC)
- 864 A
- Max. rated current of round conductor (IEC)
- 1 060 A
- Max. rated current of round conductors (UL)
- 980 A
- Указание
- The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
- The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
- Electrical ratings UL (SCCR)
- 27,5 kA - 600 V, RMS, unprotected
- 100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
- 100 kA - 600 V, Fuse Class L max. 2000 A, JDDZ/7
- Отвод проводов
- сверху/снизу
- Для шинных систем с межцентровым расстоянием
- 60 mm
- Количество полюсов
- 1-пол.
- Подходит для шинной системы
- RiLineX
- RiLine60
- Размер
- Ширина: 54,1 мм
Высота: 119,4 мм
Глубина: 163,4 мм
- Подключение проводов
- 95 ‐ 300 мм²
- Подходит для шин
- 15 x 10 мм
- 20 x 10 мм
- 30 x 10 мм
- Rated voltage
- 1 000 V AC
1 500 V DC
600 V AC (UL)
600 V DC (UL)
- Степень загрязнения
- 3
- Стандарты
- IEC/EN 61439-1
- UL 508
- Номинальное импульсное напряжение Uimp
- 12 кВ
- Номинальное напряжение изоляции Ui
- 1 000 B
- Тепловыделение макс.
- 105 Вт
- Степень защиты IP согл. МЭК 60 529
- IP 2X
- Maximum operating air humidity
- 90 %
- Диапазон рабочих температур
- -5 °C...55 °C
- Диапазон температур хранения
- -25 °C...75 °C
- Влажность воздуха (без конденсата)
- 10...90 %
- Кол-во подключений
- 2
- Fire load
- 5,947 MJ/m²
- Упаковка
- 1 шт.
- Вес нетто
- 0,8 kg
- Gross weight
- 0,892 kg
- PCF per pack (cradle-to-gate)
- 4,47
- Код ТНВЭД
- 85369010
- ETIM 9
- EC001531
- Описание продукта
-
RiLineX connection adaptor for 60 mm busbar systems. The connection adaptor is single-pole and fits a double connection (round/sector-shaped conductor). The phase spacing is freely selectable. The unit is suitable for use with L1/L2/L3/N. The adaptor boasts an impressive compact design. Dismantling requires the use of tools. Conductors may be connected either from above or below. The connection clamps support full through-wiring. Mounted by simply snapping onto the RiLineX board. The adaptor is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection.