- Št. artikla:
- SK 3314635
- Design
- Room cooling
CW - Benefits
- Individual output regulation measures the cooling output of each individual server rack
- Applications
- In conjunction with the passive and active modules of the LCP Rear Door CW portfolio
- Function principle
- Measurement of the inlet and return temperature, volumetric flow of the medium (water or water/glycol mixture), control valve actuator (PID)
- Material
- Sheet steel
Plastic
Brass
Copper - Colour
- Textured RAL 7035
- Note
- An active module is required for operation and electrical connection of the water module
- The cable harness for the water module is 5 m long.
- Dimensions
- Width: 340 mm
Height: 184 mm
Depth: 502 mm - Water connections
- DN 25 (G 1" external thread)
- Rated voltage
- 24 V DC
- Rated power input
- 0,01 kW
- Rated current
- 0,4 A
- Operating temperature range
- 10 °C...50 °C
- Permissible operating pressure (p. max.)
- 10 bar
- Water inlet temperature
- 10 °C...30 °C
- Protection category to IEC 60 529
- IP 54
- Packs of
- 1 pc(s).
- Net weight
- 11 kg
- Gross weight
- 11,9 kg
- Customs tariff number
- 84199085
- EAN
- 4028177977860
- Product description
- SK water module for LCP rear door CW for output regulation, WHD: 340x184x502 mm, RAL 7035
Water module for LCP Rear Door CW
Št. artikla: SK 3314635
Water module for individual output regulation or for determining the cooling output of an LCP rear door CW. Only suitable for use in conjunction with an active module. May be mounted either in the raised floor or above the rack, as preferred.