RiLineX connection adaptor

Št. artikla: RX 9360241

RiLineX connection adaptor for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.

Št. artikla:
RX 9360241
Benefits
Mounting on the busbar system and cable connection with just one screw
Vertical variant for side infeed to the board
Material
Polyamide (PA 6)
Fire protection corresponding to UL 94
Colour
RAL 35745
Rated current (guideline value, IEC)
432 A
Max. rated current of round conductor (IEC)
710 A
Max. rated current of round conductors (UL)
630 A
Max. rated current of laminated copper bar (IEC)
950 A
Max. rated current of laminated copper bar (UL)
910 A
Note
The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
Electrical ratings UL (SCCR)
27,5 kA - 600 V, RMS, unprotected
100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
100 kA - 600 V, Fuse Class L max. 1200 A, JDDZ/7
Cable outlet
In an axial direction to the board
For bar systems with centre-to-centre spacing
60 mm
Number of poles
3-pole
To fit busbar system
RiLineX
RiLine60
Dimensions
Width: 57.8 mm
Height: 239.4 mm
Depth: 135.6 mm
Connection of round conductors
150 ‐ 300 mm²
Clamping area for laminated copper bars (W x H)
32 x 20 mm
To fit busbars
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Rated voltage
1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
Contamination level
3
Standards
IEC/EN 61439-1
UL 508
Rated impulse withstand voltage Uimp
12 kV
Rated insulation voltage Ui
1.000 V
Heat loss max.
50 W
IP protection category to IEC 60 529
IP 2X
Maximum operating air humidity
90 %
Operating temperature range
-5 °C...55 °C
Storage temperature range
-25 °C...75 °C
Ambient humidity (non-condensing)
10...90 %
Fire load
10,554 MJ/m²
Packs of
1 pc(s).
Net weight
1 kg
Gross weight
1,185 kg
PCF per pack (cradle-to-gate)
5.51
Customs tariff number
85369010
EAN
4028177997202
ETIM 9
EC001531
Product description
RiLineX connection adaptor for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.
Odobrenja
UL + C-UL (listed)
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions
RiLineX connection adaptor (710 A)

RiLineX connection adaptor for 60 mm
busbar systems. The device has screw fastening
for simultaneous contact between the rail and conductor.
For voltages up to 1000 V AC and 1500 V DC.
IEC and UL approved.
Product information
Number of poles: 3
Busbar dimensions: 15/20/30 mm x 5/10 mm
Rated current max.: 710 A
Connection: max. 300 mm²
Cable outlet: horizontal/vertikal
Dimensions: 60 mm x 240 mm x 130 mm (WxHxD)
Manufacturer: Rittal GmbH & Co. KG
Type: 9360241