More on the product
Create PDF of this page+ Product description
Design: | non-switchable |
---|---|
Product description: | The modular system facilitates basic configuration of the racks, thanks to a vertical support rail with single-/3-phase infeed. The various socket modules to supply the active components may be snap-fitted into the support rail. The various modules, earthing pins, IEC320 etc. may be inserted into the support rail in any combination. This is easily achieved, even by non-electricians, thanks to the shock hazard protected plug & play system. |
Material: |
Section: Aluminium, anodised Socket inserts: Plastic (PA6 GF 30 V1) |
Length: | 250 mm |
Type of electrical connection: | WAGO WINSTA MIDI |
Phases per infeed: | 1~ |
Thermal overcurrent protection: | – |
Rated operating voltage: | 110 V – 230 V AC, 50/60 Hz |
Rated current (max.): | 16 A |
Required number of module slots: | 1 |
Dimensions: | Length: 250 mm |
Operating temperature range: | 5 °C...45 °C |
Ambient humidity (non-condensing): | 5...95 % |
Sockets: | 6 x IEC 320 socket C13 |
Packs of: | 1 pc(s). |
Weight/pack: | 0.332 kg |
Customs tariff number: | 85369001 |
EAN: | 4028177402539 |
ETIM 7.0: | EC000330 |
ECLASS 8.0: | 27142604 |
Product description: | DK PSM Plus socket module, C13, 6-way, black, non-switchable |
+ Approvals
Approvals: | |
---|---|
Declerations: |
Declaration of conformity:
DE, EN
|
+ Downloads / CAD
Data Sheets: | |
---|---|
Documentation: |
Instructions:
DE, EN, FR
|
+ Tender texts
Power System Module plug-in module, 6 x ICE, IEC 320
C13
Installation via the plug & play system:
The plug-in module is locked into the power system
module busbar. It can be locked in or unlocked whilst
working. The module connection direction determines
which power supply will be used.
A mixture of all of the modules can be fitted in the
busbar.
Technical fittings:
The plug-in module has 6 x IEC320 C13 sockets available
for use. The module does not have an integrated fuse.
Technical specifications:
Single-phase voltage range: 110V - 230V AC 50/60 Hz,
neutral conductor is required
Max. current per module: 10A at 230V AC, 15A at 110V AC
Temperature application range: +5°C - +45°C
Humidity range: 5% - 95% relative humidity,
non-condensing
Protection category IP20
W x H x D [mm]: 50 x 250 x 45
C13
Installation via the plug & play system:
The plug-in module is locked into the power system
module busbar. It can be locked in or unlocked whilst
working. The module connection direction determines
which power supply will be used.
A mixture of all of the modules can be fitted in the
busbar.
Technical fittings:
The plug-in module has 6 x IEC320 C13 sockets available
for use. The module does not have an integrated fuse.
Technical specifications:
Single-phase voltage range: 110V - 230V AC 50/60 Hz,
neutral conductor is required
Max. current per module: 10A at 230V AC, 15A at 110V AC
Temperature application range: +5°C - +45°C
Humidity range: 5% - 95% relative humidity,
non-condensing
Protection category IP20
W x H x D [mm]: 50 x 250 x 45