- Article number:
- DK 7338.221
- Product description
- The EFD III early fire detection system includes the smoke extraction system in a 19" subrack built into just 1 height unit. An integrated fan continuously extracts air from the area to be protected, via a pipeline system. The extracted air is passed over two fire detectors. If smoke aerosols are detected, the highly-sensitive detector emits a pre-alarm, with the second fire detector emitting the main alarm. The correct functioning of the fire detectors is monitored at all times by the evaluation and control electronics on the control board.
- Benefits
- Early fire detection
- 19" rack mount with just 1 U
- Tested by VdS Schadenverhütung GmbH
- CAN-Bus Interface to CMC III monitoring system
- Floating relay outputs (pre-alarm/main alarm/collective fault)
- Material
- Carbon steel
- Color
- Housing: RAL 7035
Front: RAL 9005
- Interfaces
- 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
- 1 x/1 x input for door contact switch (terminal/RJ12 jack)
- 2 x CAN connections for master-slave networking
- 3 x connection (external alarm/manual call point/tank and fill level)
- 1 x voltage output for DET-AC slave III (24 V DC max. 500 mA)
- 1 x USB
- 2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
- Uninterruptible mains electricity operation
- approx. 4 hrs
- Note
- The system is designed exclusively for use in closed non-accessible enclosure systems.
- Display
- Plain language display with 6 LEDs
- Sensors
- Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
- Optical smoke detector, top hat rail (sensitivity: approx. 0.25%/m light obscuration)
- Dimensions
- Width: 482.6 mm
Height: 44 mm
Depth: 490 mm( Width: 19 ˝
Height: 1.73 ˝
Depth: 19.3 ˝ )
- Operating temperature range
- 10 °C...40 °C( 50 °F...104 °F )
- Storage temperature range
- -20 °C...65 °C( -4 °F...149 °F )
- Storage temperature range, batteries
- -15 °C...40 °C
- Relative humidity (non-condensing)
- 96 %
- Rated operating voltage
- 100 V - 240 V, 1~, 50 Hz/60 Hz
- Air flow monitoring
- approx. ±10% of total air flow
- Packaging unit
- 1 pc(s).
- Net weight
- 14 kg
- Gross weight
- 15 kg
- PCF per pack (cradle-to-gate)
- 57.2 kg CO2 eq (Cat B)
- Note on PCF category
- Category B: PCF value (cradle-to-gate) based on the product weight, approximately calculated and self-declared
- Customs tariff number
- 85311095
- EAN
- 4028177699328
- ETIM 9
- EC002685
- ECLASS 8.0
- 40040104
- Product description
-