TopTherm Blue e Wall-Mounted Cooling Unit, UL Type 3R/4 1706.07 - 8530.36 BTU/h

Article number: SK 3303.518

Energy-efficient Blue e wall-mounted cooling units in output categories1706.07 - 8530.36 BTU/h with e-Comfort controller and electrical condensate evaporation integrated as standard (from 3412.14 BTU/h), protection class UL Type 3R/4, 12.

Article number:
SK 3303.518
Version
wall-mounted
Product description
Energy-efficient Blue e wall-mounted cooling units with integral e-Comfort controller and electric condensate evaporation as standard. Protection category UL Type 3R/4, 12.
Benefits
Suitable for outdoor installation
Blue e technology
May be linked to the IoT interface via the Blue e IoT adapter for cooling units with an output of 500 W or higher and e-comfort controllers
Material
Carbon steel
Color
RAL 7035
Supply includes
Condenser with hydrophobic RiNano coating
Wired ready for connection (plug-in terminal strip)
Drilling template
Fasteners
Total cooling output to DIN EN 14511
Cooling output L35 L35/60 Hz: 0.5 kW
Cooling output L35 L50/60 Hz: 0.28 kW
( Cooling output L35 L35/60 Hz: 1,706 BTU/h
Cooling output L35 L50/60 Hz: 955 BTU/h )
Rated operating voltage
115 V, 1~, 60 Hz
Rated current max.
At 60 Hz: 5.7 A
Start-up current (max.)
At 60 Hz: 11.5 A
Air throughput (unimpeded air flow)
External circuit: 345 m³/h
Internal circuit: 280 m³/h
( External circuit: 203.1 cfm
Internal circuit: 164.8 cfm )
Energy efficiency ratio (EER) 50/60 Hz L35 L35
Refrigeration factor L35 L35 (EER) 50 Hz: 1.3
Refrigeration factor L35 L35 (EER) 60 Hz: 1.35
Version
wall-mounted
Dimensions
Width: 285 mm
Height: 620 mm
Depth: 298 mm
( Width: 11.2 ˝
Height: 24.4 ˝
Depth: 11.7 ˝ )
Protection category IP to EN 60 529
External circuit, IP 34
Internal circuit IP 56
Protection category NEMA
UL Type 3R
UL Type 4
UL Type 12
Refrigerant/cooling medium
Refrigerant: R-513A
Quantity: 0.19 kg
Global Warming Potential (GWP): 631
CO₂ equivalent (CO₂e): 0.12 t
( Refrigerant: R-513A
Quantity: 0.4 lb. )
Temperature control
e-Comfort Controller (factory setting +35 °C)
Operating temperature range
-20 °C...50 °C
( -4 °F...122 °F )
Operating temperature max @60 Hz
50 °C
( 122 °F )
Operating temperature
Compressor cooling mode from +10 °C ambient temperature. Only the internal fan is active in the temperature range -20 °C to +10 °C.
Storage temperature range
-40 °C...70 °C
( -40 °F...158 °F )
Setting range
20 °C...50 °C
( 68 °F...122 °F )
Rated power Pel
Rated power L35 L35/60 Hz: 0.37 kW
Rated power L35 L50/60 Hz: 0.45 kW
Permissible operating pressure (p. max.)
28 bar
( 406.1 PSI )
Pre-fuse
Miniature circuit-breaker/fuse: 10 A
Note on Model No.:
without integral condensate evaporation
Packaging unit
1 pc(s).
Net weight
30.5 kg
Gross weight
36.5 kg
Customs tariff number
84158200
EAN
4028177943681
ETIM 9
EC000855
ETIM 8
EC000855
ECLASS 8.0
27180704
Product description
SK cooling unit Blue e, wall-mounted, 1877 BTU/h 115 V, 1~, 60 Hz, carbon steel, WHD: 285 x 620 x 298 mm
Approvals
C-UL
UL + C-UL (listed)
UL + C-UL - FTTA
Certificates
EAC
Declarations
Declaration of conformity
Declaration of conformity - F-gas regulation
Declaration of conformity UK
Documentation
Instructions – R134a
Data sheets
Safety data sheet refrigerant – R-513A
Technical System Catalogue