- Article number:
- SK 3334.300
- Benefits
- Blue e+ chillers ensure central and efficient cooling of liquid media with a high level of temperature precision and innovative DC inverter technology
- Suitable for international use due to its unique multi-voltage capability (without rewiring) and high operating limits
- Maximum safety due to integrated overflow valve and monitoring sensors
- Intuitive operation due to touch display and intelligent interfaces
- Compact and modular layout ensures minimum footprint
- Pumps with highly-efficient IE3 motors
- Color
- Textured RAL 7035
- Supply includes
- Complete unit ready for connection (plug-in terminal strip)
Multilingual documentation
- Options
- For remote monitoring and networking of cooling units and chillers, use the Blue e+ Generation IoT Interface, item number 3124.300. Increase machine availability and process safety by remote monitoring of device data, condition, and system messages.
- Protection category IP to EN 60 529
- IP 24
- IP 54 (electrics)
- Total cooling output Tw10 / Tu32
- Cooling output Tw10 Tu32/50 Hz: 2.87 kW
Cooling output Tw10 Tu32/60 Hz: 2.77 kW( Cooling output Tw10 Tu32/50 Hz: 9,793 BTU/h
Cooling output Tw10 Tu32/60 Hz: 9,452 BTU/h )
- Total cooling output Tw18 / Tu32
- Cooling output Tw18 Tu32/50 Hz: 4.18 kW
Cooling output Tw18 Tu32/60 Hz: 4.08 kW( Cooling output Tw18 Tu32/50 Hz: 14,263 BTU/h
Cooling output Tw18 Tu32/60 Hz: 13,922 BTU/h )
- Total cooling output to DIN EN 14511 Tw18 / Tu35
- Cooling output Tw18 Tu35/50 Hz: 4 kW
Cooling output Tw18 Tu35/60 Hz: 3.9 kW
- Air throughput (unimpeded air flow)
- At 50 Hz: 1,850 m³/h
At 60 Hz: 1,850 m³/h( At 50 Hz: 1,088.9 cfm
At 60 Hz: 1,088.9 cfm )
- Rated operating voltage
- 380 V - 415 V, 3~, 50 Hz
- 440 V - 480 V, 3~, 60 Hz
- Dimensions
- Width: 450 mm
Height: 820 mm
Depth: 710 mm( Width: 17.7 ˝
Height: 32.3 ˝
Depth: 28 ˝ )
- Note
- When the software is downloaded, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these license conditions.
- Temperature control
- e+ controller (factory setting +20 °C)
- Operating temperature range
- -5 °C...50 °C( 23 °F...122 °F )
- Storage temperature range
- -40 °C...70 °C( -40 °F...158 °F )
- Operating temperature range of cooling medium
- 5 °C...35 °C( 41 °F...95 °F )
- Temperature hysteresis
- ± 0.5 K
- Refrigerant/cooling medium
- Refrigerant: R-513A
Quantity: 0.7 kg
Global Warming Potential (GWP): 631
CO₂ equivalent (CO₂e): 0.44 t( Refrigerant: R-513A
Quantity: 1.5 lb. )
- Pump pressure
- At 50 Hz: 2.9 bar
- Volumetric flow (cooling medium)
- At 50 Hz: 15 l/min
- Rated power Pel
- At 50 Hz: 2.63 kW
At 60 Hz: 2.9 kW
- Rated current max.
- At 50 Hz: 4 A
At 60 Hz: 3.8 A
- Pre-fuse
- Miniature circuit-breaker/fuse: 15 A
- Refrigeration factor (EER) 50 Hz Tw18 / Tu35 DIN EN 14511
- 2.53
- Water circuit
- hermetically open
- Water connections
- ¾" internal thread
- Number of cooling circuits
- 1
- Tank
- Material: Plastic PE
Volume: 12 l
- Packaging unit
- 1 pc(s).
- Net weight
- 90 kg
- Gross weight
- 107 kg
- Customs tariff number
- 84186900
- EAN
- 4028177809840
- ETIM 9
- EC002516
- ETIM 8
- EC002516
- ECLASS 8.0
- 27180713