- Article no.:
- RX 9360.000
- Benefits
- Time saving through complete digital product data
- Shorter mounting time thanks to pre-mounted complete board
- Tested short circuit resistance up to max. 65 kA
- Suitable for applications in the alternating current range up to 1,000 V AC and direct current up to 1,500 V DC
- Contact hazard protection up to IP 2XB, can be upgraded to IP 3X
- Tested and certified to IEC and UL
- Simple extension and baying
- Material
- Upper part: carbon steel, zinc-plated
Contact plate: E-Cu, tin-plated
Front cover: polyamide (PA 6)
Fire behavior corresponding to UL 94 - Color
- RAL 35745
- Supply includes
- 3 rail connectors
1 front cover
1 insulating plate - Protection category IP to IEC 60 529
- IP 2XB
- Standards
- IEC 61 439-1/-2
- UL 508
- Rated current max.
- 780 A
- Rated current (UL)
- 780 A
- Electrical UL ratings (SCCR)
- 52.5 kA - 600 V, RMS
- 100 kA - 600 V, fuse class L max. 1600 A, JDDZ/7
- 100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
- 100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
- 65 kA - 600 V, circuit breaker max. 800 A, DIVQ/7
- Rated impulse withstand voltage UImp
- 12 kV
- Rated voltage
- 1,000 V AC
1,500 V DC
600 V AC (UL)
600 V DC (UL) - Rated insulation voltage
- 1,000 V AC
1,500 V DC - Rated impulse withstand current
- 103 kA
115.5 kA - Rated short-time withstand current/t
- 45 kA/200 ms
52.5 kA/500 ms - Overvoltage category
- 4
- Contamination level
- 3
- Number of poles
- 3-pole
- Fundamental frequency
- 50...60 Hz
- Ambient humidity (non-condensing)
- 10...90 %
- Suitable for busbars
- 30 x 5/10 mm
- Operating temperature range
- -5 °C...55 °C( 23 °F...131 °F )
- Dimensions
- Width: 153 mm
Height: 240 mm
Depth: 77 mm( Width: 6.02 ˝
Height: 9.45 ˝
Depth: 3.03 ˝ ) - Packaging unit
- 1 pc(s).
- Net weight
- 1.88 kg
- Gross weight
- 1.924 kg
- Copper weight (kg per piece)
- 0.297
- Customs tariff number
- 85369010
- EAN
- 4028177997431
- ETIM 9
- EC002270
- Product description
- RX baying set incl. connector for RiLineX Board 3-pole
RiLineX baying set for board
Article no.: RX 9360.000
RiLineX baying connector set for the complete board, for use with 550 A and 800 A. Comprising a busbar connector and contact hazard protection cover. For simple baying of boards between two bayed VX enclosures, no drilling required.