- Article no.:
- RX 9360200
- Benefits
- Easy mounting
- Material
- Polyamide (PA 6)
Fire behavior corresponding to UL 94
- Color
- RAL 9005
- Rated current (guideline value, IEC)
- 67 A
- Max. rated current of round conductor (IEC)
- 76 A
- Max. rated current of round conductors (UL)
- 66 A
- Note
- The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
- The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
- Electrical UL ratings (SCCR)
- 5 kA - 600 V, RMS, unprotected
- 35 kA - 480 V, circuit breaker max. 60 A, DIVQ/7
- 100 kA - 600 V, fuse class J max. 100 A, JDDZ/7
- Cable outlet
- Top/bottom
- For bar systems with center-to-center spacing
- 60 mm
- Number of poles
- 3-pole
- Suitable for busbar system
- RiLineX
- RiLine60
- Dimensions
- Width: 26.8 mm
Height: 239.2 mm
Depth: 103.3 mm( Width: 1.06 ˝
Height: 9.42 ˝
Depth: 4.07 ˝ )
- Connection of round conductors
- 1.5 ‐ 16 mm²
- Suitable for busbars
- 12 x 5/10 mm
- 15 x 5/10 mm
- 20 x 5/10 mm
- 30 x 5/10 mm
- Rated voltage
- 800 V AC
800 V DC
600 V AC (UL)
600 V DC (UL)
- Contamination level
- 3
- Standards
- IEC/EN 61439-1
- UL 508
- Rated impulse withstand voltage UImp
- 8 kV
- Rated insulation voltage Ui
- 800 V
- Power loss max.
- 7 W( 24 BTU/h )
- Protection category IP to IEC 60 529
- IP 2X
- Maximum operating air humidity
- 90 %
- Operating temperature range
- -5 °C...55 °C( 23 °F...131 °F )
- Storage temperature range
- -25 °C...75 °C( -13 °F...167 °F )
- Ambient humidity (non-condensing)
- 10...90 %
- For busbar thickness
- 5 ‐ 10 mm( 0.2 ‐ 0.39 ˝ )
- Fire load
- 6.79 MJ/m²
- Packaging unit
- 4 pc(s).
- Net weight
- 1.2 kg
- Gross weight
- 1.656 kg
- PCF/VE (cradle-to-gate)
- 13.4
- Customs tariff number
- 85369010
- EAN
- 4028177997264
- ETIM 9
- EC001531
- Product description
-
RiLineX connection adapter for 60 mm busbar systems. The adapter boasts an impressive compact design and simple conductor connection. Dismantling requires the use of tools. Round conductors may be connected either from above or below. The push-in connection clamps are designed for easier connection. Mounted by simply snapping onto the RiLineX board. The distinguishing features of the connection adapter include a high current-carrying capacity and high short-circuit resistance, plus universal contact hazard protection which adapts to the relevant wire gage. The device features semi-automatic adjustment of the busbar thickness between 5 and 10 mm.