- Article no.:
- RX 9360241
- Benefits
- Mounting on the busbar system and cable connection with just one screw
- Vertical version for feeding the board from the side
- Material
- Polyamide (PA 6)
Fire behavior corresponding to UL 94
- Color
- RAL 35745
- Rated current (guideline value, IEC)
- 432 A
- Max. rated current of round conductor (IEC)
- 710 A
- Max. rated current of round conductors (UL)
- 630 A
- Max. rated current of laminated copper bar (IEC)
- 950 A
- Max. rated current of laminated copper bar (UL)
- 910 A
- Note
- The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
- The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
- Electrical UL ratings (SCCR)
- 27.5 kA - 600 V, RMS, unprotected
- 100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
- 100 kA - 600 V, fuse class L max. 1200 A, JDDZ/7
- Cable outlet
- Axial to the board
- For bar systems with center-to-center spacing
- 60 mm
- Number of poles
- 3-pole
- Suitable for busbar system
- RiLineX
- RiLine60
- Dimensions
- Width: 57.8 mm
Height: 239.4 mm
Depth: 135.6 mm( Width: 2.28 ˝
Height: 9.43 ˝
Depth: 5.34 ˝ )
- Connection of round conductors
- 150 ‐ 300 mm²
- Clamping area for laminated copper bars (W x H)
- 32 x 20 mm( 1.26 x 0.79 ˝ )
- Suitable for busbars
- 15 x 5/10 mm
- 20 x 5/10 mm
- 30 x 5/10 mm
- Rated voltage
- 1,000 V AC
1,500 V DC
600 V AC (UL)
600 V DC (UL)
- Contamination level
- 3
- Standards
- IEC/EN 61439-1
- UL 508
- Rated impulse withstand voltage UImp
- 12 kV
- Rated insulation voltage Ui
- 1,000 V
- Power loss max.
- 50 W( 171 BTU/h )
- Protection category IP to IEC 60 529
- IP 2X
- Maximum operating air humidity
- 90 %
- Operating temperature range
- -5 °C...55 °C( 23 °F...131 °F )
- Storage temperature range
- -25 °C...75 °C( -13 °F...167 °F )
- Ambient humidity (non-condensing)
- 10...90 %
- Fire load
- 10.554 MJ/m²
- Packaging unit
- 1 pc(s).
- Net weight
- 1 kg
- Gross weight
- 1.185 kg
- PCF/VE (cradle-to-gate)
- 5.51
- Customs tariff number
- 85369010
- EAN
- 4028177997202
- ETIM 9
- EC001531
- Product description
-
RiLineX connection adapter for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.