This item will be discontinued on: Mar 30, 2025
- Article no.:
- DK 7979513
- Product description
- High-end power distribution in compact design for IT network and server racks. With energy measurement per single output slot.
- Benefits
- For vertical mounting, it may be attached in the zero-U space of the Rittal VX IT or TS IT rack with no need for tools
- Color coding of phases and backup circuits (L1 = pink, L2 = black, L3 = white)
- Tool-free installation kit for VX IT
- Self-powered PDU, no external power supply necessary
- Measurement accuracy ± 1% (kWh) according to EN 62 053-21
- Integrated real-time clock with battery buffering (max. 10 years, battery replaceable)
- Integrated electromagnetic buzzer for acoustic alarm
- Adjustable limit values (warning/alarm) for current, voltage, output, individual settings for each output slot
- Energy-saving design, low energy consumption
- Technical specifications
- Display/controller unit in PDU enclosure, 180° rotation, replaceable
- Integrated, fully redundant power supply, power supply from all phases
- Fault-tolerant PDU power supply redundant across all phases
- Voltage V, current A, frequency Hz
- Active power, active energy, apparent power, apparent energy
- Power factor (cosPhi) and phase angle
- Neutral conductor measurement/load imbalance detection
- Fuse monitoring for PDUs with integrated fuse
- Bright TFT display 128 x 128 pixels (RGB) with back-lighting and energy-saving mode (display of output data and PDU configuration)
- Position sensors for display rotation and correct PDU display on the website
- Multi-colored LEDs (green/amber/red) to indicate switching states and limits per individual output slot
- Power LED for indicating voltage
- Material
- Aluminum section, black anodized
Slots: plastic - Supply includes
- Assembly components
- Options
- Type 3 overvoltage protection with interchangeable arresters while operational, with status monitoring, suitable for integration into PDU enclosure
Differential current measurement (type B) per infeed/phase/fuse
Monitoring of the optional overvoltage protection
CMC III CAN bus sensors may be connected for ambient monitoring, max. 16 sensors
Other enclosure colors possible - Measurement functions, description
- Measurement per phase or infeed
- Additional measurement per output slot
- Powerful CPU (ARM Cortex A8)
- Digital input (floating contact)
- Additional alarm output/relay output (changeover contact)
- Dimensions
- Width: 44 mm
Depth: 70 mm
Length: 1,095 mm( Width: 1.73 ˝
Depth: 2.76 ˝
Length: 43.1 ˝ ) - Number of sockets and type
- 12 x C13 / 4 x C19
- Outlets
- 12 x C 13
4 x C 19 - Rated operating voltage
- 230 V (AC)
- Rated current (max.)
- 32 A
- Rated power
- 7.4 kW
- Infeeds
- Qty.: 1
Phases per infeed: 1~ - Length of connection cable
- 3 m( 118 ˝ )
- Type of connection (electrical)
- CEE
- Interfaces
- USB 2.0 port (USB-A) for bulk configuration, firmware update & data logging
- CAN bus interface (RJ45) far a maximum of 16 ambient sensors
- RS232 serial interface (RJ12) for LTE unit, scripting, CLI
- Use of own certificates/TLS 1.2
- Email sending in case of alarm (SMTP)
- User management including rights management
- LDAP(S)/Radius/Active Directory connection
- Syslog server connection (maximum 2 servers)
- Fully redundant Ethernet interface 10/100/1000 Mbit/s
- Number RJ45 ports for sensor units max
- 2
- Guidelines
- EMC Directive 2014/30/EU
- Low-Voltage Directive 2014/35/EU
- Standards
- EN 62368-1
- EN 61000-3
- EN 61000-4
- EN 61000-6
- EN 62053-21
- Protocols
- Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP
- TCP/IP v4 & v6, DHCP, DNS
- SNMP v1, v2c & v3, Modbus/TCP, OPC-UA
- MIB for use in 3rd party DCIM software
- FTP/SFTP (update/file transfer)
- Operating temperature range
- 5 °C...50 °C( 41 °F...122 °F )
- Ambient humidity (non-condensing)
- 10...95 %
- Storage temperature range
- -20 °C...70 °C( -4 °F...158 °F )
- Suitable for
- Enclosure type: VX IT enclosure frame: ≥ 1,200 mm
Enclosure type: VX IT 19" profile rails: ≥ 1,800 mm( Enclosure type: VX IT enclosure frame: ≥ 47.2 ˝
Enclosure type: VX IT 19" profile rails: ≥ 70.9 ˝ ) - Packaging unit
- 1 pc(s).
- Net weight
- 4.5 kg
- Gross weight
- 4.5 kg
- Customs tariff number
- 85366990
- EAN
- 4028177948327
- ETIM 9
- EC002762
- ETIM 8
- EC002762
- ECLASS 8.0
- 27142604
- Product description
- DK PDU metered+, compact basic power distribution incl. energy measurement per output, with network interface and display, WLD: 44x1095x70 mm, IEC 60 320: 12x C13, 4x C19
- Software
- Software