Blue e+ roof-mounted cooling unit Total cooling output 1.30 kW
Model No. 3185.730
Product Lifecycle
Active
More on the product
Create PDF of this page– Recommended accessories
+ Product description
Benefits: |
Average 75% energy savings thanks to speed-regulated components and heat pipe technology Suitable for international use due to a unique multi-voltage capability Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling Intuitive operation due to touch display and intelligent interfaces |
---|---|
Material: | Sheet steel |
Colour: | RAL 7035 |
Supply includes: |
Blue e+ roof-mounted cooling unit Pleated filter Fully wired ready for connection Assembly parts Condensate hose (3 m) |
Options: | For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages. |
Total cooling output to DIN EN 14511: |
Cooling output L35 L35/50 Hz: 1.3 kW Cooling output L35 L35/60 Hz: 1.3 kW Cooling output L35 L50/50 Hz: 0.76 kW Cooling output L35 L50/60 Hz: 0.76 kW |
Rated operating voltage: |
110 V - 240 V, 1~, 50 Hz/60 Hz 380 V - 480 V, 3~, 50 Hz/60 Hz |
Note: |
Only suitable for mounting on enclosures with minimum dimensions (W x D) 800 x 600 mm Operation without a pleated filter is inadmissible By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions. |
Rated power input: | 0,75 kW |
Air throughput (unimpeded air flow): |
External circuit: 750 m³/h Internal circuit: 700 m³/h |
Energy efficiency ratio (EER) 50/60 Hz L35 L35: |
Refrigeration factor L35 L35 (EER) 50 Hz: 2.04 Refrigeration factor L35 L35 (EER) 60 Hz: 2.04 |
Seasonal energy efficiency ratio (SEER) 50/60 Hz: | 5,3 |
Design: | roof-mounted |
Dimensions: |
Width: 700 mm Height: 308 mm Depth: 560 mm |
Protection category to IEC 60 529: |
External circuit IP 54 with pleated filter Internal circuit IP 54 with pleated filter |
Refrigerant/cooling medium: |
Refrigerant: R134a Quantity: 0.59 kg Global Warming Potential (GWP): 1,430 CO₂ equivalent (CO₂e): 0.85 t |
Type of electrical connection: | Plug-in terminal strip |
Temperature control: | e+ controller (factory setting +35 °C) |
Operating temperature range: | -20 °C...55 °C |
Storage temperature range: | -40 °C...70 °C |
Operating temperature range of refrigerant circuit (active): | 3 °C...55 °C |
Heat pipe operating temperature range: | -20 °C...45 °C |
Setting range: | 20 °C...50 °C |
Power consumption Pel: |
Power consumption L35 L35/50 Hz: 0.67 kW Power consumption L35 L35/60 Hz: 0.67 kW Power consumption L35 L50/50 Hz: 0.68 kW Power consumption L35 L50/60 Hz: 0.68 kW |
Permissible operating pressure (p. max.): | 24 bar |
Packs of: | 1 pc(s). |
Weight/pack: | 38 kg |
Customs tariff number: | 84158200 |
EAN: | 4028177927155 |
ETIM 7.0: | EC000855 |
ECLASS 8.0: | 27180704 |
Product description: | SK roof-mounted cooling unit Blue e+,, Sheet steel,, cooling module, 1.3 kW,, 110-240 V, 1~, 50/60 Hz, 380-480 V, 3~, 50/60 Hz, WHD: 700 x 308 x 560 mm |
+ Approvals
Approvals: | |
---|---|
Certificates: |
EAC:
RU
|
Declerations: |
+ Add accessories
+ Tender texts
3185.730
SK Blue e+ roof-mounted cooling unit
Revolutionary energy efficiency with innovative hybrid technology.
Average 75% energy savings thanks to speed-regulated components and heat
pipe technology. Unique multi-voltage capability for worldwide use.
Intuitive operation via touch display.
Total cooling output L35 L35 50/60 Hz: 1,3 / 1,3 kW
Total cooling output L35 L50 50/60 Hz: 0,76 / 0,76 kW
Power consumption L35 L35 50/60 Hz: 0,67 / 0,67 kW
Power consumption L35 L50 50/60 Hz: 0,61 / 0,61 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions: [WxHxD]:700x308x560 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,04
Refrigeration factor (SEER) 50/60 Hz: 5,3
Refrigeration / Quantity: R134a / 590 g
Operating temperature: -20 °C to 55 °C
Setting range: 20 °C to 50 °C
Storage temperature: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 54 with
pleated filter, External circuit IP 54 with pleated filter
Weight: 38 kg
SK Blue e+ roof-mounted cooling unit
Revolutionary energy efficiency with innovative hybrid technology.
Average 75% energy savings thanks to speed-regulated components and heat
pipe technology. Unique multi-voltage capability for worldwide use.
Intuitive operation via touch display.
Total cooling output L35 L35 50/60 Hz: 1,3 / 1,3 kW
Total cooling output L35 L50 50/60 Hz: 0,76 / 0,76 kW
Power consumption L35 L35 50/60 Hz: 0,67 / 0,67 kW
Power consumption L35 L50 50/60 Hz: 0,61 / 0,61 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions: [WxHxD]:700x308x560 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 2,04
Refrigeration factor (SEER) 50/60 Hz: 5,3
Refrigeration / Quantity: R134a / 590 g
Operating temperature: -20 °C to 55 °C
Setting range: 20 °C to 50 °C
Storage temperature: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 54 with
pleated filter, External circuit IP 54 with pleated filter
Weight: 38 kg