Product details
Energy-efficient Blue e+ wall-mounted cooling units in output categories 1600 W to 5800 W. Average energy savings of 75% can be achieved with speed-regulated components and heat pipe technology. Available in sheet steel and stainless steel versions.
More on the product
Create PDF of this page– Recommended accessories
+ Product description
Product description: | For mounting the roof-mounted unit. The cut-out in the door is arranged so that the roof-mounted cooling unit is positioned centrally on the door. |
---|---|
Benefits: |
Average 75% energy savings thanks to speed-regulated components and heat pipe technology Suitable for international use due to a unique multi-voltage capability Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling Intuitive operation due to touch display and intelligent interfaces |
Material: | Stainless steel 1.4301 (AISI 304) |
Colour: | RAL 9007 |
Supply includes: |
Condenser with hydrophobic RiNano coating Integral electric condensate evaporation Assembly parts Fully wired ready for connection (plug-in terminal strip) |
Options: | For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages. |
Total cooling output to DIN EN 14511: |
Cooling output L35 L35/50 Hz: 2.6 kW Cooling output L35 L35/60 Hz: 2.6 kW Cooling output L35 L50/50 Hz: 1.82 kW Cooling output L35 L50/60 Hz: 1.82 kW |
Rated operating voltage: |
110 V - 240 V, 1~, 50 Hz/60 Hz 380 V - 480 V, 3~, 50 Hz/60 Hz |
Note: |
Please observe the mounting instructions. By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions. Only suitable for use in semi-outdoor areas (see instructions for description) |
Note on Model No.: | Tolerance: 110 V -10% (99 V) and 240 V +10% (264 V) / 380 V -10% (342 V) and 480 V +6% (509 V) |
Rated power input: | 1,05 kW |
Air throughput (unimpeded air flow): |
External circuit: 1,250 m³/h Internal circuit: 1,250 m³/h |
Energy efficiency ratio (EER) 50/60 Hz L35 L35: |
Refrigeration factor L35 L35 (EER) 50 Hz: 2.63 Refrigeration factor L35 L35 (EER) 60 Hz: 2.63 |
Seasonal energy efficiency ratio (SEER) 50/60 Hz: | 6,2 |
Design: | wall-mounted |
Dimensions: |
Width: 450 mm Height: 1,600 mm Depth: 294 mm |
Required mounting cut-out: |
Cut-out width: 433 mm Cut-out height: 1,579 mm |
Protection category to IEC 60 529: | Internal circuit IP 55 |
Protection category NEMA: | UL Type 3R/12 |
Refrigerant/cooling medium: |
Refrigerant: R134a Quantity: 1.15 kg Global Warming Potential (GWP): 1,430 CO₂ equivalent (CO₂e): 1.64 t |
Temperature control: | e+ controller (factory setting +35 °C) |
Operating temperature range: | -20 °C...60 °C |
Storage temperature range: | -40 °C...70 °C |
Operating temperature range of refrigerant circuit (active): | 3 °C...60 °C |
Heat pipe operating temperature range: | -20 °C...45 °C |
Setting range: | 20 °C...50 °C |
Power consumption Pel: |
Power consumption L35 L35/50 Hz: 0.99 kW Power consumption L35 L35/60 Hz: 0.99 kW Power consumption L35 L50/50 Hz: 0.94 kW Power consumption L35 L50/60 Hz: 0.94 kW |
Permissible operating pressure (p. max.): | 24 bar |
Packs of: | 1 pc(s). |
Weight/pack: | 54,8 kg |
Customs tariff number: | 84158200 |
EAN: | 4028177934672 |
ETIM 7.0: | EC000855 |
ECLASS 8.0: | 27180704 |
Product description: | SK cooling unit Blue e+, wall-mounted, 2.6 kW, 110-240 V, 1~, 380-480 V, 3~, 50-60 Hz, Stainless steel, WHD: 450 x 1600 x 294 mm |
+ Approvals
Approvals: | |
---|---|
Certificates: |
EAC:
RU
|
Declerations: |
+ Add accessories
+ Tender texts
3187630
Wall-mounted cooling unit Blue e+
A revolution in energy efficiency using innovative hybrid technology.
Average 75% energy savings with speed-regulated components and heat pip
technology. Unique multi-voltage capability for worldwide use. Intuitiv
operation via touch display.
Total cooling output L35 L35 50/60 Hz: 2,6 / 2,6 kW
Total cooling output L35 L50 50/60 Hz: 1,82 / 1,82 kW
Power consumption L35 L35 50/60 Hz: 0,99 / 0,99 kW
Power consumption L35 L50 50/60 Hz: 0,94 / 0,94 kW
Rated power input: 1,05 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 450x1600x294 mm
Material: Stainless steel 1.4301 (AISI 304)
Colour: RAL 9007
Refrigeration factor (EER) 50/60 Hz: 2,63 / 2,63
Refrigeration factor (SEER) 50/60 Hz: 6,2
Refrigerant / Quantity: R134a / 1150 g
Operating temperature range: -20 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 55
Weight: 54,8 kg
Wall-mounted cooling unit Blue e+
A revolution in energy efficiency using innovative hybrid technology.
Average 75% energy savings with speed-regulated components and heat pip
technology. Unique multi-voltage capability for worldwide use. Intuitiv
operation via touch display.
Total cooling output L35 L35 50/60 Hz: 2,6 / 2,6 kW
Total cooling output L35 L50 50/60 Hz: 1,82 / 1,82 kW
Power consumption L35 L35 50/60 Hz: 0,99 / 0,99 kW
Power consumption L35 L50 50/60 Hz: 0,94 / 0,94 kW
Rated power input: 1,05 kW
Rated operating voltage: 110-240 V, 1~, 50/60 Hz; 380-480 V, 3~, 50/60
Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 450x1600x294 mm
Material: Stainless steel 1.4301 (AISI 304)
Colour: RAL 9007
Refrigeration factor (EER) 50/60 Hz: 2,63 / 2,63
Refrigeration factor (SEER) 50/60 Hz: 6,2
Refrigerant / Quantity: R134a / 1150 g
Operating temperature range: -20 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 55
Weight: 54,8 kg