Product details
Energy-efficient Blue e+ wall-mounted cooling units in output categories 1600 W to 5800 W. Average energy savings of 75% can be achieved with speed-regulated components and heat pipe technology. Available in sheet steel and stainless steel versions.
More on the product
Create PDF of this page– Recommended accessories
+ Product description
Product description: | For mounting the roof-mounted unit. The cut-out in the door is arranged so that the roof-mounted cooling unit is positioned centrally on the door. |
---|---|
Benefits: |
Average 75% energy savings thanks to speed-regulated components and heat pipe technology Suitable for international use due to a unique multi-voltage capability Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling Intuitive operation due to touch display and intelligent interfaces |
Material: | Stainless steel 1.4301 (AISI 304) |
Colour: | RAL 9007 |
Supply includes: |
Condenser with hydrophobic RiNano coating Integral electric condensate evaporation Assembly parts Fully wired ready for connection (plug-in terminal strip) |
Options: | For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages. |
Total cooling output to DIN EN 14511: |
Cooling output L35 L35/50 Hz: 4.2 kW Cooling output L35 L35/60 Hz: 4.2 kW Cooling output L35 L50/50 Hz: 3.02 kW Cooling output L35 L50/60 Hz: 3.02 kW |
Rated operating voltage: | 380 V - 480 V, 3~, 50 Hz/60 Hz |
Note: |
Please observe the mounting instructions. By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions. Only suitable for use in semi-outdoor areas (see instructions for description) |
Note on Model No.: |
Tolerance: 380 V -10% (342 V) and 480 V +5% (509 V) Full installation not possible |
Rated power input: | 1,3 kW |
Air throughput (unimpeded air flow): |
External circuit: 2,300 m³/h Internal circuit: 2,300 m³/h |
Energy efficiency ratio (EER) 50/60 Hz L35 L35: |
Refrigeration factor L35 L35 (EER) 50 Hz: 3.46 Refrigeration factor L35 L35 (EER) 60 Hz: 3.46 |
Seasonal energy efficiency ratio (SEER) 50/60 Hz: | 8,1 |
Design: | wall-mounted |
Dimensions: |
Width: 450 mm Height: 1,600 mm Depth: 393 mm |
Required mounting cut-out: |
Cut-out width: 433 mm Cut-out height: 1,579 mm |
Protection category to IEC 60 529: | Internal circuit IP 55 |
Protection category NEMA: | UL Type 3R/12 |
Refrigerant/cooling medium: |
Refrigerant: R134a Quantity: 1.75 kg Global Warming Potential (GWP): 1,430 CO₂ equivalent (CO₂e): 2.5 t |
Temperature control: | e+ controller (factory setting +35 °C) |
Operating temperature range: | -20 °C...60 °C |
Storage temperature range: | -40 °C...70 °C |
Operating temperature range of refrigerant circuit (active): | 3 °C...60 °C |
Heat pipe operating temperature range: | -20 °C...45 °C |
Setting range: | 20 °C...50 °C |
Power consumption Pel: |
Power consumption L35 L35/50 Hz: 1.21 kW Power consumption L35 L35/60 Hz: 1.21 kW Power consumption L35 L50/50 Hz: 1.28 kW Power consumption L35 L50/60 Hz: 1.28 kW |
Permissible operating pressure (p. max.): | 24 bar |
Packs of: | 1 pc(s). |
Weight/pack: | 71,2 kg |
Customs tariff number: | 84158200 |
EAN: | 4028177934665 |
ETIM 7.0: | EC000855 |
ECLASS 8.0: | 27180704 |
Product description: | SK cooling unit Blue e+, wall-mounted, 4.2 kW, 380-480 V, 3~, 50-60 Hz, Stainless steel, WHD: 450 x 1600 x 393 mm |
+ Approvals
Approvals: | |
---|---|
Certificates: |
EAC:
RU
|
Declerations: |
+ Add accessories
+ Tender texts
3188640
Wall-mounted cooling unit Blue e+
A revolution in energy efficiency using innovative hybrid technology.
Average 75% energy savings with speed-regulated components and heat pip
technology. Unique multi-voltage capability for worldwide use. Intuitiv
operation via touch display.
Total cooling output L35 L35 50/60 Hz: 4,2 / 4,2 kW
Total cooling output L35 L50 50/60 Hz: 3,02 / 3,02 kW
Power consumption L35 L35 50/60 Hz: 1,21 / 1,21 kW
Power consumption L35 L50 50/60 Hz: 1,28 / 1,28 kW
Rated power input: 1,3 kW
Rated operating voltage: 380-480 V, 3~, 50/60 Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 450x1600x393 mm
Material: Stainless steel 1.4301 (AISI 304)
Colour: RAL 9007
Refrigeration factor (EER) 50/60 Hz: 3,46 / 3,46
Refrigeration factor (SEER) 50/60 Hz: 8,1
Refrigerant / Quantity:R134a / 1750 g
Operating temperature range: -20 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 55
Weight: 71,2 kg
Note: Full installation not possible
Wall-mounted cooling unit Blue e+
A revolution in energy efficiency using innovative hybrid technology.
Average 75% energy savings with speed-regulated components and heat pip
technology. Unique multi-voltage capability for worldwide use. Intuitiv
operation via touch display.
Total cooling output L35 L35 50/60 Hz: 4,2 / 4,2 kW
Total cooling output L35 L50 50/60 Hz: 3,02 / 3,02 kW
Power consumption L35 L35 50/60 Hz: 1,21 / 1,21 kW
Power consumption L35 L50 50/60 Hz: 1,28 / 1,28 kW
Rated power input: 1,3 kW
Rated operating voltage: 380-480 V, 3~, 50/60 Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 450x1600x393 mm
Material: Stainless steel 1.4301 (AISI 304)
Colour: RAL 9007
Refrigeration factor (EER) 50/60 Hz: 3,46 / 3,46
Refrigeration factor (SEER) 50/60 Hz: 8,1
Refrigerant / Quantity:R134a / 1750 g
Operating temperature range: -20 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
Protection category IP to IEC 60 529: Internal circuit IP 55
Weight: 71,2 kg
Note: Full installation not possible