- Številka izdelka:
- RM 7857.971
- Design
- Basic protection plus room
- Product description
- The basic protection room - an optimum, modular room-within-a-room solution for protecting IT/infrastructure components. The High Availability room - certified maximum physical protection for data centres and IT system locations.
- Note
- Tested products are tested as a complete construction. This comprises the cellular structure and installation modules such as doors, cable shields or ventilation units. By contrast, component testing only refers to individual parts.
- Corrosive fire gases
- Acrid gas-tightness, based on EN 1634-3 (DIN 18095)
- Falling debris
- Shock test as system test, 1 shock of 200 kg from 1.5 m after 30 minutes flame impingement time
- Dust-tightness
- IP 5x as system testing to EN 60 529, for the cellular structure and its built-in modules
- EMC protection
- Protection against high-frequency irradiation and radiation, verified by tests on comparable components by TU Aachen
- Fire protection
- 50 K temperature rise and 85% rel. humidity over 30 minutes, without reheat period
- F90 as system test, according to the limits of EN 1363 (DIN 4102), for the cellular structure and its built-in modules
- F120 only as component testing to EN 1363 (DIN 4102), wall system only
- F90 only as component testing to EN 1363 (DIN 4102), wall system only
- Unauthorised access
- RC 3 as system test to EN 1627/1630, for the cellular structure and its built-in modules, such as doors
- RC 2 as system test to EN 1627/1630, for the cellular structure and its built-in modules, such as doors
- Water
- Extinguisher water, IP x6 as system testing to IEC 60 529, for the cellular structure and its built-in modules
- Relative humidity, 85%, over 30 minutes
- Packs of
- 1 pc(s).
- EAN
- 4028177689367
- ETIM 7.0
- EC002499
- ECLASS 8.0
- 27180207
- Product description
- RM Security room, Basic protection room plus (GSR+)