Product details
For mounting on the roof surface. Cooling output 1.87 kW – 4 kW. Protection category IP 55 as standard. Particularly suitable for use in harsh environments. Flexible water connection options.
More on the product
Create PDF of this page+ Product description
Design: | Water-carrying parts, copper/brass (Cu/CuZn) |
---|---|
Product description: | For use in harsh environments and temperature ranges up to +70 °C. The air/water heat exchanger is assembled on the roof of the enclosure using flexible water connection options. |
Colour: | RAL 7035 |
Supply includes: |
Fully wired ready for connection (plug-in terminal strip) Drilling template Sealing mat Assembly parts |
Total cooling output: | L 35 W 10 at 400 l/h: 2.5 kW |
Rated operating voltage: | 115 V, 1~, 50 Hz/60 Hz |
Power consumption Pel: |
At 50 Hz: 98 W At 60 Hz: 115 W |
Rated current max.: |
At 50 Hz: 0.85 A At 60 Hz: 0.95 A |
Permissible operating pressure (p. max.): | 1 ‐ 10 bar |
Type of electrical connection: | Plug-in terminal strip |
Duty cycle: | 100 % |
Cooling medium: | Water (see Internet for specifications) |
Water inlet temperature: | 1 °C...30 °C |
Water connections: |
½" connector sleeve G ⅜" external thread |
Temperature control: | Basic controller (factory setting +35 °C) |
Operating temperature range: | 1 °C...70 °C |
Dimensions: |
Width: 597 mm Height: 417 mm Depth: 475 mm |
Note on Model No.: | Extended delivery times. |
Protection category: | IP 65 available on request |
Pre-fuse: | Miniature circuit-breaker/fuse: 4 A |
Setting range: | 20 °C...55 °C |
Protection category to IEC 60 529: | IP 55 |
Packs of: | 1 pc(s). |
Weight/pack: | 27.5 kg |
Customs tariff number: | 84195080 |
EAN: | 4028177429826 |
ETIM 7.0: | EC002515 |
ECLASS 8.0: | 27180712 |
+ Approvals
Approvals: | |
---|---|
Declerations: |
Declaration of conformity:
DE, EN
|
+ Add accessories
+ Tender texts
Roof-mounted air/water heat exchanger
For use in tough environments. Flexible water
connection options.
Total cooling output L 35 W 10, 400l/h: 2.5 kW
Rated operating voltage: 115 V, 50/60 Hz
Refrigerant: Water (see specifications)
Water-carrying parts: Cu/CuZn
Dimensions [W x H x D]: 597 x 417 x 475 mm
Ambient temperature range: 1°C to 70°C
Setting range: 20°C to 55°C
Water inlet temperature range: 1°C to 30°C
Temperature control and monitoring: Basic controller
(factory setting 35 °C)
Type of connection: Plug-in terminal strip
Protection category to IEC 60 529: IP 55
Weight: 27.5 kg
Colour: RAL 7035
For use in tough environments. Flexible water
connection options.
Total cooling output L 35 W 10, 400l/h: 2.5 kW
Rated operating voltage: 115 V, 50/60 Hz
Refrigerant: Water (see specifications)
Water-carrying parts: Cu/CuZn
Dimensions [W x H x D]: 597 x 417 x 475 mm
Ambient temperature range: 1°C to 70°C
Setting range: 20°C to 55°C
Water inlet temperature range: 1°C to 30°C
Temperature control and monitoring: Basic controller
(factory setting 35 °C)
Type of connection: Plug-in terminal strip
Protection category to IEC 60 529: IP 55
Weight: 27.5 kg
Colour: RAL 7035