Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC

Article number: SK 3311.440

Ideal for cooling small and medium-sized IT applications.

Article number:
SK 3311.440
Version
LCP Inline DX
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimizes the power consumption of the fans
Temperature monitoring and control.
Redundant temperature sensor integrated at the air end
Due to the speed-regulated compressor, the cooling output adapts to the actual requirements
Special maintenance of the LCP DX due to separation of cooling and server enclosures
Using LCP DX/FC variants in combination with indirect free cooling helps to save operating costs
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
LCP for use within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling
The LCP DX/FC versions contain both refrigerant as well as a water/glycol heat exchanger. A free cooler is also integrated in the external condenser.
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
Material
Carbon steel, spray finished
Options
Humidifier
Dehumidification and reheater
Condensate lift pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Version
Row Cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L30: 12 kW
Useful cooling output L22 L45: 10 kW
( Useful cooling output L22 L45: 34,121 BTU/h )
Modulation range
3 ‐ 12 kW
Total cooling output/number of fan modules
12 kW/4
( 40,946 BTU/h )
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
( At 50 Hz: 2,825.2 cfm )
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
( Width: 11.8 ˝
Height: 78.7 ˝
Depth: 47.2 ˝ )
Suitable for enclosure type
TS IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 60 Hz
400 V, 3~, 50 Hz
Rated current max.
At 50 Hz: 7.5 A
Max. cooling output
12 kW
( 40,946 BTU/h )
Type of connection (electrical)
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Infinitely variable fan control
Inverter-controlled compressor
Pre-fuse
Miniature circuit-breaker/fuse: 20 A
Storage temperature range
-20 °C...50 °C
( -4 °F...122 °F )
Operating temperature range
15 °C...35 °C
( 59 °F...95 °F )
Noise pressure level
At 50 Hz: 69 dB(A)
Protection category IP to EN 60 529
IP 20
Packaging unit
1 pc(s).
Weight/packaging unit
233.5 kg
( 514.8 lb. )
Customs tariff number
84195080
EAN
4028177691346
ETIM 8
EC002515
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Product description
SK LCP Inline DX, Refrigerant-based split cooling unit for suite cooling, Mounted on the side of the rack, flush, Cooling of several racks, Support of IT-compatible, #front-to-back# air routing,
Certificates
EAC
Declarations
Declaration of conformity
Data sheets
Drawings
Safety data sheet
Technical Data sheet